aVS303

The AVS303 is a Three Phase Automatic Voltage Switcher which 

protects against over voltage and under voltage on any one of the 

three phases as well as loss of one or more phases. indication and/or 

disconnection as a result of mains frequency error of phase sequence 

error is available as an option.

The VS303 incorporates a contactor to switch the full load current. 

The AVS303-xx is available in different sizes ranging from 23Amps to 

1250Amps (the -xx relates to the model number, ie: AVS303-23 is a 23Amp 

per phase AVS303).

The options for the AVS303 are:

Frequency error (oPT/01)

Phase sequence error (oPT/02)

or both (oPT/03)

operation

make sure that your load does not exceed the rating of the AVS303.

The limits of the AVS303 are set for a window of 190-260 volts line to neutral. if a

different window is required, please refer to your dealer.

if an option board is fitted please ensure the d.i.l. switches are set correctly as

detailed in the separate instructions.

connections of the three phases from the mains (incoming cABLE) and to the

load (oUTgoing cABLE) are made to the contractor.it is essential that the incoming

nEUTrAL is connected to the terminal block.

on first switching on, there will be no output for approximately one minute while

the AVS303 monitors the mains. For that period the yellow LEd indicates that the mains are 

within acceptable limits, after which the green LEd goes on and the load is connected. The red 

LEd indicates that the mains is outside the window, and the load is disconnected.

Frequency and Phase Error indications, where fitted, are by separate red LEds.

14

15

wiring

From the incoming mains:

1.   connect neutral to the neutral on the terminal block

2.   connect Phase 1 to where the rEd wirE is connected on the contactor

3.   connect Phase 2 to where the yELLow wirE is connected on the contactor

4.   connect Phase 3 to where the BLUE wirE is connected on the contactor

For the outgoing mains:

 mirror the above connections.

rEd = phase 1

yELLow = phase 2

BLUE = phase 3

  model  AVS303 

 

 

  model AVS303

  current (Amps) 

23 to1250 

 

  nominal voltage(V) 

230/400 

 

  wait time (mins) 

10 secs to 10 minutes 

 

  Under-voltage disconnect(V) 

190V (150 - 230V) 

 

  over-voltage disconnect(V) 

260V (150 - 230V, also off) 

 

  hysteresis(V) 

 

  Socket type 

direct via brass screw terminal 

 

  Fused plug 

n/A 

 

 

  rFi protection 

no 

 

  Transient suppression 

yes >6.5kA 

 

  Spike protection(J) 

160 

 

SpeciFicationS

1.

2.

3.

4.

5.

6.

Содержание AVS30

Страница 1: ...yle 14 Industrial Estate newlands drive Poyle Slough SL3 0dX United Kingdom Tel International 44 1753 688300 National 01753 688300 Fax International 44 1753 685306 National 01753 685306 E mail sales s...

Страница 2: ...se major problems for home and business computing An unpredictable power supply can lead to worrying problems such as surges spikes lightning strikes brown outs power cuts black outs power back surges...

Страница 3: ...ent Power supply has returned to normal after an under voltage condition see below The AVS is waiting before the power supply is restored to your equipment The AVS has detected low voltage condition a...

Страница 4: ...hen change the settings on potentiometer marked WAIT Settings are available in increments up to 10 minutes You can also set the WAIT dial to MAN While on MAN the AVS30 will not reconnect the mains unl...

Страница 5: ...Connector terminals Refer to connection terminals layout diagram on next page 4 Insert cable to appliance through the Cordgrip Bush and connect to the Connector terminals 5 Tighten the Cordgrip Bushe...

Страница 6: ...nd the appliance switched on and off to prevent activating the time delay every time the appliance is switched on Connection CAUTION IF THE AVS IS ALREADY WIRED MAKE SURE IT IS DISCONNECTED FROM THE M...

Страница 7: ...AVS3P 0 wiring diagram Diagram three R N C C N O S T N A1 T1 L1 L2 T2 T3 L3 A2 N R N C C N O S T N R N C C N O S T N To The Load Live to Contactor Coil Live from other control Option C Option A AVS3P...

Страница 8: ...ctor It is essential that the incoming NEUTRAL is connected to the terminal block On first switching on there will be no output for approximately one minute while the AVS303 monitors the mains For tha...

Страница 9: ...pert Lightning Basic Lightning High Voltage Power Back Surges Advanced Lightning Low Voltage Spikes Surges RFI Noise Power Cuts Telecom Surges Expert Lightning High Voltage Power Back Surges Advanced...

Страница 10: ...o mechanical faults as equipment is stopped while in operation What causes it Power or sub station failure breakdown in the distribution network or simply a plug being pulled out accidentally Power Ba...

Отзывы: