Sollatek AVS30 Скачать руководство пользователя страница 7

13

12

aVS3p-0

The AVS3P-0 is an Automatic Voltage Switcher designed to protect three 

phase loads from voltage fluctuations, over voltage, under voltage, surges, 

dips and frequent start/stops. The output is a single volt-free changeover 

contact, rated at 16A. This is intended to control an external contactor, 

control circuit, start/stop system or alarm. if the voltage on any one phase 

goes above or below the pre-set limits (the ‘window’), then the AVS

will switch off. once the voltage returns within the window limits, the 

AVS will wait for a pre-set time, continuing to check the voltages, before 

automatically turning the load back on. The over voltage, under voltage 

and delay settings are all adjustable using controls in the terminal compartment of the AVS3P. The 

standard window that is considered acceptable is 185V-260V(320V-450V three phase). outside these 

limits electronic and electrical equipment are likely to be damaged.

operation

connect the AVS in accordance with the wiring diagram opposite (fig 1). Ensure that the r, S 

& T sensing connections to the AVS come from the supply side of the contactor. note: a good 

neutral connection must be provided from the supply.
The output from the AVS is a changeover relay with volt-free contacts. There is a common (c), 

a normally open (no) and normally closed (nc) contacts. when the AVS3P-0 is in the red or 

Amber condition then c is connected to nc. when the AVS3P-0 displays green then c is

connected to no. make sure that the control current you wish to switch does not exceed the 

rating of the AVS3P-0 relay (max 16Amps).
if the AVS is the only thing to control the contactor (or load, or alarm, etc), then the ‘c’ and ‘no’ 

AVS contacts can be used to connect power to the contactor coil (method A). if however, there 

are other circuits/equipment that also must control the contactor, then the AVS contacts can be 

used to interrupt the contactor coil supply from there (method B) or used in conjunction with a 

start/stop or other system, e.g. method c.

Figure 1. 

AVS3P-0 

wiring 

diagram

Diagram three

R

N
C

C N

O

S T N

A1

T 1

L1 L2

T 2 T 3

L3

A2

N

R

N
C

C N

O

S T N

R

N
C

C N

O

S T N

To The Load

Live to contactor coil

Live from

other control

(option c)

(option A)

AVS3P-0

contactor

Three Phase Sense wires

Switched Live to contactor coil

To Stop control

From 24V dc

To Start control

(option B)

 model  AVS3P-0 

 

 

  

115V 

240V

 current (Amps) 

16A@230V   

16A@230V

 nominal voltage(V) 

115/220V 

230/240V

 wait time (mins) 

10 secs to 10mins 

10 secs to 10mins 

 window limits 

adjustable 

adjustable 

 hysteresis(V) 

2

 

 Socket type 

                                                     direct via brass screw terminal  

 Fused plug 

n/A 

n/A 

 

 rFi protection 

no 

no 

 Attenuation(db) 

no 

no

 Transient suppression 

yes 

 Spike protection(J) 

80J@115V 

160J@230V

 max consumption 

35VA 

35VA

 max supply (phase to neutral) 

160V 

320V

SpeciFicationS

1.

2.

3.

   led colour  

Indicating

  

load Status

 

red  

High incoming voltage

  

oFF

 

yellow  

AVS is in wait state after a high voltage transition

 

oFF

   green  

Mains normal

  

on

 

yellow  

AVS is in wait state after a low voltage transition

 

oFF

   red  

Low incoming voltage

  

oFF

Five LEds accurately display the status 
of the AVS in the following symmetrical 
traffic light design:

OFF

Wait

ON

Wait

OFF

HIGH

LOW

Set limits of the AVS3P-0 using the thumb-wheel adjustment inside the terminal compartment. 

See fig 2. Ensure that limits set are safe for the load being protected. For example: Low =185V 

and high = 260V is normally considered safe for most equipment but you should check with the 

equipment manufacturer’s information.
Set the time delay control using the thumb-wheel adjustment inside the terminal compartment. 

This will depend on your load and how it is operated. As a general guide, compressors and 

refrigeration equipment will need at least 3 minutes; motors, pumps, etc should not be started 

too frequently so may be 2 minutes minimum, electronic loads 0.5 minutes. The ‘off’ position 

gives just 10 seconds. The equipment manufacturer should be consulted on the best setting.
At first switching on, there will be no output during the delay period. For that period the yellow 

LEd indicates that the mains supply is within acceptable limits, after which the green LEd goes 

on and the output relay changes state to turn the load on.

4.

5.

6.

Содержание AVS30

Страница 1: ...yle 14 Industrial Estate newlands drive Poyle Slough SL3 0dX United Kingdom Tel International 44 1753 688300 National 01753 688300 Fax International 44 1753 685306 National 01753 685306 E mail sales s...

Страница 2: ...se major problems for home and business computing An unpredictable power supply can lead to worrying problems such as surges spikes lightning strikes brown outs power cuts black outs power back surges...

Страница 3: ...ent Power supply has returned to normal after an under voltage condition see below The AVS is waiting before the power supply is restored to your equipment The AVS has detected low voltage condition a...

Страница 4: ...hen change the settings on potentiometer marked WAIT Settings are available in increments up to 10 minutes You can also set the WAIT dial to MAN While on MAN the AVS30 will not reconnect the mains unl...

Страница 5: ...Connector terminals Refer to connection terminals layout diagram on next page 4 Insert cable to appliance through the Cordgrip Bush and connect to the Connector terminals 5 Tighten the Cordgrip Bushe...

Страница 6: ...nd the appliance switched on and off to prevent activating the time delay every time the appliance is switched on Connection CAUTION IF THE AVS IS ALREADY WIRED MAKE SURE IT IS DISCONNECTED FROM THE M...

Страница 7: ...AVS3P 0 wiring diagram Diagram three R N C C N O S T N A1 T1 L1 L2 T2 T3 L3 A2 N R N C C N O S T N R N C C N O S T N To The Load Live to Contactor Coil Live from other control Option C Option A AVS3P...

Страница 8: ...ctor It is essential that the incoming NEUTRAL is connected to the terminal block On first switching on there will be no output for approximately one minute while the AVS303 monitors the mains For tha...

Страница 9: ...pert Lightning Basic Lightning High Voltage Power Back Surges Advanced Lightning Low Voltage Spikes Surges RFI Noise Power Cuts Telecom Surges Expert Lightning High Voltage Power Back Surges Advanced...

Страница 10: ...o mechanical faults as equipment is stopped while in operation What causes it Power or sub station failure breakdown in the distribution network or simply a plug being pulled out accidentally Power Ba...

Отзывы: