7.1
Digital Input And Output Ports
7.1.1
Common Options
Figure 7-1 Digital Input / Output Ports Option
Valid Time
CIE-M10 recognizes its digital input ports‟ signals only if the signal keeps a pre-specified
time (Valid Time). If the signal doesn‟t remain for the pre-specified time(Valid Time), this
signal will be ignored.
Delay
CIE-M10 will output a value to the output port after waiting for [Delay] ms.
In order to do so, the signal value must last for [Delay] seconds. If the output value does
not last for the [Delay] seconds, CIE-M10 will not send that signal to the output port.
If the [Delay] value is set as 0, CIE-M10 will send the output value to the output port
immediately.
The [Delay] is used for Modbus/TCP, Macro, HTTP, and other functions provided by CIE-
M10. The unit used for the [Delay] is 1ms. However, since the accuracy is only guaranteed