CIE-H10A User Manual Ver. 1.1
- 11 -
1.6
Interface
1.6.1
Input Ports
Because each of CIE-H10A
’
s input ports are isolated by photo-couplers, users don
’
t need
to worry about the polarity. The circuit of the input port is shown in the figure below.
Figure 1-7 a circuit of the input port
The voltage specification of the input port is as follows:
Over 2.2V
H
1
Under 1.2V
L
0
Max. Input Voltage
24V
Polarity
Auto Polarity
Table 1-3 the voltage specification of the input ports
The input port is interfaced with a 5mm terminal block. Thus, use a (-) shaped
screwdriver to connect it with the user device.
⚫
Types for giving input
The type of the input ports is a wet contact by photo-couplers, which needs two
wires with different voltage levels to make an input signal. Needed a dry contact, you
can use a DCA(Dry Contact Adapter) so that you can give an input signal (ON or
HIGH) with switch (relay) interface.
The input ports are designed only for monitoring signals.