Installing the VHF/UHF AOR – Rack Mounting
The VHF/UHF AOR can be installed in a 19-inch equipment rack, where it requires 4U of rack space. It
can mount either above or below the MRU.
1- Position the unit in the rack.
When positioning the unit in the rack, make sure to leave 2U of space between it and the MRU to allow
for cable installation and air circulation.
2- Insert the M6 screws in the mounting holes and tighten the screws to secure the chassis.
11.4
Installing Power Cabling
The VHF/UHF AOR supports both DC-48V and AC120V for input power. Make sure to order the
appropriate power unit according to your installation requirements. Based on your configuration, SOLiD
will ship the unit with the correct power supply installed and provide the correct power cable with the
connector attached.
All connections are made at the back of the unit. The power connector is slotted and can only be installed
one way. For your information, the following table shows the power connections.
MC Connector
Numbering
Lug Naming
AOR PSU Terminal naming
AC
DC
AC
DC
A
AC_H
-48V
AC-H
-48V
B
AC_N
GND
AC-N
IN_GND
C
GND
DC NC
FG
FG
Table 11.2 – VHF/UHF AOR Power Connections
Figure 11.4 – VHF/UHF AOR Power Port
1- Connect the power cable to the PSU and to the power source.
2- Power on the unit to verify power is connected properly.