62
| Round fire damper manual 02/2021
SOLID AIR ®
CLIMATE SOLUTIONS
•
T +31 598 36 12 21
•
www.solid-air.com
•
7. Maintenance and operation
TRANSPORT
After arrival, check the fire damper for transport
damage and shortcomings. In case of any damage or
shortcomings, immediately contact your supplier.
STORAGE
If the damper is not installed immediately:
• Remove any wrapping.
• Protect fire damper from dust and contamination.
• Do not expose the fire damper to the effects of
weather - store fire damper in dry place.
• Do not store the unit below -20 °C or above 50 °C.
Please properly dispose of packaging material
MAINTENANCE AND OPERATION
Klimaoprema fire dampers are designed with fully
enclosed drive mechanism outside of the duct and as
such do not require cleaning and regular maintenance.
However, activation mechanism should be inspected
for proper operation on regular basis.
• Provide at least one annual check of the damper
• After each intervention, provide a systematic
cleaning of dust and especially the solenoid and
its movable plate
• Check the if the electrical terminals are tightened.
It is not permitted to alter the dampers in any way
nor perform any changes (except for the service
procedures described in this manual) to their structure
without the manufacturer’s consent.
Provide at least one annual check of the damper.
The functional test must be carried out in compliance
with the basic maintenance principles of the European
norms EN 13306, EN 15423 and EN15650.
COMMISSIONING
1. Carefully unpack FDC fire damper - be careful of
sharp edges and do not use excessive force for
unpacking.
2. Inspect the fire damper - check the fire damper for
damage.
3. Installation of the fire damper - according to the
installation instructions (page 13).
4. Before commissioning: check the fire damper
functions.
FUNCTIONS
1. Release mechanism: Damper blade can be closed
and opened manually.
2. EMS: Signal testing - the damper blade must close.
3. Electric actuator: Signal testing - the damper blade
must close/open.
4. Thermal fuse: By a button - the damper blade
must be closed by pressing the button.