This air conditioner is equipped with an LCDI (Leakage Current Detection and Interruption) power cord 

and plug as required by US National Electric Code 440.65. This cord consists of a length of shielded flexi-

ble cord with no termination on the load side and a LCDI attachment plug on the line side.

 

 

The LCDI power cord and plug will remove the supply source via electrical disconnect (circuit trip) if the 

nominal current leakage between the cord shield and either load conductor exceeds a predetermined value. 

The cord will remain de

-

energized until the device has been manually reset. This is intended to reduce the 

risk of a fire in the power cord or combustible materials nearby. The cord shields are not grounded and they 

must be considered a shock hazard if exposed. The cord shield must not be connected to ground or to any 

exposed metal.

 

 

The test and reset buttons on the LCDI Plug are used to check if the plug is functioning properly. 

 

To test: 

 

 

1.

 

Plug power cord into wall outlet, the LED light will turn on.

 

2.

 

Press TEST Button, circuit should trip, cutting power to the air conditioner. When this occurs, the LED 

light will turn off. 

 

3.

 

Press RESET button to restore power to the unit. Once power is restored, the LED light will turn on.

 

 

If test button is pressed and unit can still be turned on, current leakage has been detected. Do not use the air 

conditioner or attempt to reset the LCDI Plug. Contact Customer Service for troubleshooting recommenda-

tions. 

 

 

 

 

 

 

 

 

 

 

 

                                      

 

 

 

 

 

 

 

 

WARNING:

 

 

1. DO NOT press the TEST button while the air conditioner is operating.

 

2. The TEST and RESET buttons should not be used as 

ON

” 

and 

OFF

” 

switches.

 

3. The cord and plug are not intended to offer protection to externally connected loads or supply circuits.

 

4. The cord and plug are intended for indoor use only.

 

 

 

POWER CORD AND PLUG

 

RESET

 

TEST

 

LED LIGHT

 

Note: Your unit

s power cord may 

 

           differ from the one shown.

 

Содержание WM1-05M2-02

Страница 1: ...er must be upright for 24 hours prior to operating This ensures that the compressor will function as intended Model WM1 05M2 02 5 100 BTU Window Air Conditioner Operating Instructions AIR CONDITIONER...

Страница 2: ...itioner please read this owner s manual carefully Store this manual in a safe place for future reference Your safety and the safety of others is very important to us Please pay attention to all safety...

Страница 3: ...sed metal The test and reset buttons on the LCDI Plug are used to check if the plug is functioning properly To test 1 Plug power cord into wall outlet the LED light will turn on 2 Press TEST Button ci...

Страница 4: ...Rail Foam Seal Insert Strip Short Screw Long Screw Sash Lock Curtain Lock Window Air Conditioner 1 Top Mounting Rail 1 Insert Strip 1 Short Screw 8 Long Screw for Locking Bracket Curtains 12 Side Cur...

Страница 5: ...ions W x H x D 16 125 x 11 75 x 15 125 Package Dimensions W x H x D 17 9 x 14 96 x 17 2 Net Gross Weight Lbs 40 7 45 1 Refrigerant Type R 410A Plug Type NEMA 5 15P SPECIFICATIONS Noise level is measur...

Страница 6: ...ENTED IN THIS USER S MANUAL ARE THE PRESENATION OF THE MANUFACTURER SOLEUS N A HAS NOT CONDUCTED AN INDEPENDENT TEST TO VERIFY THE INFORMATION AND SPECIFICATIONS PRESENTED HEREWITHIN WARNING grounding...

Страница 7: ...sill The board or wood piece should have a depth of at least 1 1 2 Make sure the board or piece of wood is approximately 1 2 higher than the storm window frame This will allow the air conditioner to...

Страница 8: ...uter case using four short screws Curtain Installation 1 Insert the side curtains into the upper and lower rails of the air conditioner Fasten the curtains to the unit with short screws as shown below...

Страница 9: ...the air conditioner and window sill This is option al Foam Seal Window Sill Sash Lock Curtain Locks Flange Curtain Remove the Air Conditioner from the Window End of Season 1 Turn the air conditioner o...

Страница 10: ...ettings or turn the selector counter clockwise to select the lower cool settings Turn the MODE selector to OFF to turn off the unit FAN MODE Turn the MODE selector counter clockwise to select HIGH FAN...

Страница 11: ...LOSS OF POWER PROTECTION If power to the air conditioner is lost or interrupted the air conditioner will automatically re start in the setting last used prior to power loss AIR DIRECTION Use the leve...

Страница 12: ...D TEAR To minimize wear and tear on the air conditioner always wait at least 3 minutes before changing modes This will help prevent the compressor from overheating and the circuit breaker from trippin...

Страница 13: ...not stay engaged discontinue use of the air conditioner and contact a qualified service technician The Air Conditioner does not cool as it should Airflow is restricted Make sure there are no curtains...

Страница 14: ...correctly tilted towards the outside For proper water drainage make sure the air conditioner is slightly tilted downward from the front of the unit to the rear Water collects in the base pan Moisture...

Страница 15: ...al handling provisions in the in structions Damage to the finish of the case or other appearance parts caused by wear Damage caused by repairs or alterations of the unit by anyone other than those aut...

Отзывы: