background image

COMPRESSOR 

The compressor is hermetically sealed, permanently lubri-

cated and requires no additional oiling. 

FRONT PANEL AND GRILLE 

The front panel and grille can be cleaned with a mild soap  

or 

detergent.  Do not use hydrocarbon-based cleaners (e.g. 

acetone, benzene, naphtha, gasoline, etc.) to clean the front 

panel or grille. Use care when cleaning the control area. 

Do 

not use an excessively wet cleaning cloth. 

SCHEDULED MAINTENANCE 

To achieve continuing top performance and high efficiency, 

a regular cleaning/inspection schedule must be established. 

Maintaining this schedule can be accomplished by either a 

local maintenance staff or an authorized servicer and must 

follow the instructions described in this manual. 

• If the unit is operated in a dusty climate, dust may 

collect 

in the basepan and clog the condenser coil.

I

t is 

advisable to remove the unit from the sleeve and thor-

oughly clean the basepan and condenser coil on a

periodic basis. 

• If the unit is installed ocean side or in a corrosive 

atmosphere, its life may be greatly reduced by the

corrosive environment. Under these conditions, the unit 

should be removed from the sleeve and completely

cleaned once a year.  At that time any scratches or

blisters on the painted surfaces should be sanded and

repainted. 

OUTDOOR COIL CLEANING 

The coils on the outdoor side of the air conditioner should be 

checked regularly. For cleaning outside coil, remove the 6 

screws that mount the condenser coil top cover to condenser 

shroud. 

Normal Operating Sounds and Conditions 

POPPING OR GURGLING SOUNDS 

This sound is the refrigerant traveling through the lines. 

   

This 

is a normal sound which may be heard for a few seconds after 

the unit shuts off. 

WATER TRICKLING SOUNDS 

This sound is produced by the water as it is picked up and 

run over the coils. This procedure improves the efficiency of 

the unit and helps with water removal. 

WATER DRIPPING 

Water will collect in the basepan during high humidity days. 

STARTING DELAY 

You may notice a short delay in the startup if you try to restart 

the unit too soon after turning it off or if you adjust the 

thermostat right after the compressor has shut off.  This 

delay protects the compressor. 

Obtaining Service

In the unlikely event this unit requires repair or servicing 

beyond what is covered in this manual, contact an autho-

rized service organization. 
To obtain an authorized servicer, contact your sales repre-

sentative or agency. 

ADDITIONAL  THINGS  YOU  SHOULD  KNOW 

Now that you have mastered the operating procedure, here are more features in your control that you should know. 

The Remote Control will operate all the control panel features, follow the same instructions. 

The "Cool "circuit has an automati

3 minute time delayed start if the unit is turned off 

and on quickly. This prevents overheating of the compressor and possible circuit 
breaker tripping. The fan will continue to run during this time. 

The control will maintain any set temperature between 60F and 90F degrees (cooling), 55F and 80F (heating). 

The control is capable of displaying temperature in degrees Fahrenheit or degrees Celsius. To convert from 

one to the other, press and hold the Up and Down Temperature Selection Pads at the same time for 3 

seconds. 

13

Содержание SG-TTW-09ESE-26

Страница 1: ...Electronic Through the Wall Air Conditioner Operating Instructions Models SG TTW 09ESE 26 SG TTW 12ESEZ 26 SG TTW 09HC 26 SG TTW 12HC 26...

Страница 2: ...ng installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the productsafelyandto...

Страница 3: ...oling Capacity BTU Hr 9 200 9 200 8 900 11 800 11 800 11 400 Rated heating Capacity BTU Hr N A 11 000 9 000 N A 11 000 9 000 Cooing Power Input Watt 940 940 910 1 260 1 200 1 160 Heating Power Input W...

Страница 4: ...t claims from dealers for transportation damage Unpacking The Unit 1 Cut the carton banding and open the carton 2 Remove the literature hardware pack upper styrofoam shipping blocks and styrofoam corn...

Страница 5: ...with the wall sleeve for a complete description of the installation proce dure NOTE Wallsleeve PBWS01A isnotshippedwithchassis and must be purchased separately Wall Sleeve Outside Wall Outside Inside...

Страница 6: ...to the sleeve Ensure that the ground wire is not pinched or in the path of the condenser fan 5 Loosen locking plate screw and rotate tab with tab behind wall case flange See Figure C then tighten lock...

Страница 7: ...ted and conditioned When set at OPEN some inside air is exhausted outside Locating Locating Hole Hole Screw Hole Screw Hole OPEN position CLOSE position Mesh end toward back Mesh end toward front Figu...

Страница 8: ...the following warnings and cautions WARNING To avoid the risk of electrical shock personal injury or death do not service this unit without first opening all disconnects and or removing the unit cord...

Страница 9: ...RE TIME TURNS UNIT ON OR OFF TIMER DISPLAYS TEMPERATURE TIME TURNS UNIT ON OR OFF TIMER SLEEP MODE 22 81 7 ELECTRONIC CONTROL OPERATING INSTRUCTIONS Before you begin thoroughly familiarize yourself wi...

Страница 10: ...on to turn SLEEP mode on or off SLEEP mode is set to off automatically When SLEEP mode is selected the timer can be adjusted SLEEP mode is not available in Fan or Auto mode Press the FAN button to tur...

Страница 11: ...mer The Auto on time can be set between 5 24 hours The icons T ON and H will flash for 5 seconds Start select ing the time using the and but tons before the icons stop flashing The time will increase...

Страница 12: ...show the LOCK icon in which case the lock icon will flash three times when a key is pressed After the keypad is unlocked the lock icon on the display will disappear When the unit is on the default is...

Страница 13: ...N YOU WILL SEE DO THIS PRESS FAN SPEED BUTTON SELECT AUTO FAN 10 Note Tap or hold either up or down v button until the desired temperature is seen on display This temperature will be automatically mai...

Страница 14: ...er mode after 5 seconds and the Timer light will turn on In Timer mode The set temp and fan speeds will be saved The LED displays the set temperature not the current room temperature Press the Timer o...

Страница 15: ...ned anywhere between 61 F 16 C and 86 F 30 C When the set room temperature is reached the fan will cycle off and on to circulate and sample the room air FAULT CODES SLEEP FEATURE YOU WILL SEE DO THIS...

Страница 16: ...Conditions POPPING OR GURGLING SOUNDS This sound is the refrigerant traveling through the lines This is a normal sound which may be heard for a few seconds after the unit shuts off WATER TRICKLING SOU...

Страница 17: ...Damage caused by repairs or alterations of the unit by anyone other than those authorized by Soleus Interna tional Inc Freight and Insurance cost for the warranty service Filter and Accessories ALL WA...

Отзывы: