background image

13

Before Calling Service

To reduce the risk of electric shock, personal injury, or death, turn the fan control to the

off position and remove the unit plug from the wall outlet before doing any inspection or

maintenance work.

WARNING

The following is a list of problems that are sometimes encountered when using a room air conditioner.  Possible cause and
suggested remedies are given for each problem.
If the problem cannot be fixed using the suggested remedies, see 

WHEN SERVICE IS REQUIRED

 section.

PROBLEM 

POSSIBLE CAUSE 

SUGGESTED REMEDY 

UNIT WILL NOT RUN 

No power to unit 

Push reset button on power cord. 

Set Fan Control to position other than OFF. 

Make sure plug is firmly seated in outlet. 

Check for blown fuses, tripped circuit breakers. 

LITTLE OR NO COOLING 

LITTLE OR NO HEATING 
(fan 

and

 compressor run) 

Fresh air/exhaust damper open 

Obstructed indoor or outdoor airflow 

Dirty air filters 

Unit undersized for application 

Set vent to CLOSED. 

Remove obstruction from indoor grille or outdoor louvers. 

Dirty air filter. Clean or replace, as needed. 

Check with dealer to determine proper capacity unit for application. 

LITTLE OR NO COOLING 

LITTLE OR NO HEATING 
(only fan runs) 

Temperature Control not set properly 

For cooling, turn Temperature Control to cooler setting. 

For heating, turn Temperature Control to warmer setting. 

NOISY UNIT 

Loose front on mounting assembly 

Weak building construction 

Water hitting fan blade 

Unit oversized for application: 
compressor cycles on and off frequently 

Tighten any loose parts. 

Provide additional support for unit. 

Normal in high humidity. Stop noise by removing drain plug or 
adding condensate drain cup. 

Check with dealer to determine proper capacity unit for application. 

MOUNTING SUPPORT NOT 
INSTALLED 

Storm window frame installed in window 

Some models require removal of storm window frame before 
installation. 

FROST ON INDOOR COIL 

Dirty air filter 

Normal for low outdoor temperatures 

Clean air filter by vacuuming or washing with water and mild soap. 

Turning Temperature Control to warmer setting reduces occurrence 
and duration of frost. 

FROST ON OUTDOOR COIL 
(heat pump models only) 

Normal for outdoor temperatures at or 
below 45°F 

Call for service 

only

 if unit does not heat room and you have 

checked all problems and remedies listed under LITTLE OR NO 
HEATING. 

ODORS IN COOLING 

Mold, mildew, or algae formation on wet 
surfaces 

To reduce algae growth, use algaecide tablet in base pan; remove 
drain plug; add condensate drain cup and hose. Thoroughly clean 
unit. 

ODORS IN HEATING 

Normal for first time electric heater is 
used each season 

Caused by dust accumulation during unused months. 

Odor dissipates quickly with heater use. 

 

Содержание KC-45H

Страница 1: ...BTU Room Air Conditioner with Heat Pump OPERATING AND INSTALLATION MANUAL Model KC 45H Thank you for selecting Soleus Air To ensure proper operation please read this manual and keep it for future refe...

Страница 2: ...UCTIONS 6 11 OPERATING CONTROLS 12 BEFORE CALLING SERVICE 13 WHEN SERVICE IS REQUIRED 14 ANY QUESTIONS 14 THROUGH THE WALL INSTALLATION INSTRUCTIONS 15 16 SPECIFICATION 17 WARRANTY 18 Thank you for se...

Страница 3: ...arranty Service line at 1 888 8 SOLEUS If your problem cannot be resolved by phone contact an authorized Soleus Air brand servicer Contact and service will be at your expense Safety Information Be sur...

Страница 4: ...appliance or light fixture ReceptacleWiring Receptacle wiring must be of adequate size for unit Refer to unit identification plate for exact power requirements Minimum size of wiring based on power r...

Страница 5: ...separately Through the wallinstallationinstructionsareincluded with the outer case These models can be adapted to window installation by purchasing an optional mount ing kit RoomHeatPumps Heatpumpswo...

Страница 6: ...lter Cleaning A dirty air filter reduces operating efficiency of unit Filter should be inspected at least once every week during opera tion Cleanfilterwithvacuumcleanerorwashinwarmwater and mild deter...

Страница 7: ...outdoor coil surface This is the sound of water you hear during normal operation The water quickly evaporates on this warm surface and improves the efficiency of your air conditioner In normal condit...

Страница 8: ...properly grounded 3 prong wall outlet Some models require 230 208 volt a c protected with a time delay fuse or circuit breaker These models should be installed on their own single branch circuit for...

Страница 9: ...7 Installation Instruction Continuous...

Страница 10: ...piece of wood to the stool WOOD PIECES WIDTH 2 LENGTH Long enough to fit inside the window frame THICKNESS To determine the thickness place a piece of wood on the stool to make it 1 2 higher than the...

Страница 11: ...OW A Carefully slide the case into the window and center the case Lower the window behind the top mounting rail Pull the bottom of the case forward so that the bottom mounting rail is tight against th...

Страница 12: ...weak or if the weight of the air conditioner falls between the studs in the wall F Extend the left and right accordion panels to the vertical window sashes Drill pilot holes and attach the top and bot...

Страница 13: ...bottom corners and pull it forward Unhook it from its top hinges and set it aside F Using the tab pull up slightly on the filter to release it and pull it down and out 8 INSTALL THE AIR CONDITIONER IN...

Страница 14: ...GH HEAT Filters and circulates room air with the fan running continuously on high speed Also heats while the compressor or electric heater is running Select this setting for maximum air circulation an...

Страница 15: ...ature Control to cooler setting For heating turn Temperature Control to warmer setting NOISY UNIT Loose front on mounting assembly Weak building construction Water hitting fan blade Unit oversized for...

Страница 16: ...quent failure of unit voids warranty Warranty details are contained in warranty certificate enclosed with unit Keep accurate records of service calls including what was done servicer s name and date o...

Страница 17: ...m side to side Use wood shims between sides of case and finished opening especially where case is secured to opening to prevent warping or distorting Check installed case for distortion using carpente...

Страница 18: ...se is properly positioned in opening use wood shims to fill any gaps between case and finished opening especially in area where case will be secured to opening Take care not to warp or distort case wh...

Страница 19: ...e Highside 340 P S I Cooling AMPS 9 7 8 9 Cooling Watts 1955 2000 Cooling EER 9 0 Heating AMPS 8 8 8 3 Heating Watts 1790 1850 Heating EER 9 2 Electric Heat AMPS 15 6 16 Electric Heat Watts 3600 Air F...

Страница 20: ...ect accident incorrect power line voltage fire flood or other Acts of God or normal wear and tear Warranty service must be performed by a qualified HVAC contractor Soleus maintains a centralized servi...

Отзывы: