VOLTAGE MEASUREMENTS
Once the unit is properly wired, measure the unit supply
voltage. Voltage must fall within the voltage utilization
range given in
.
Chart 3
WIRING
Cord connection to a wall socket is not permitted for 265V
units. All 265V units must be hard wired using the hard
wire kit or make use of the plug in receptacle in the
standard subbase.
230~208V units are equipped with LCDI
power cords and
can open the electrical circuit to the unit. In the event the
unit does not operate, check the reset button located on or
near the head of the power cord as part of the normal
trouble shooting procedure.
WARNING
HIGH VOLTAGE
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING
THIS UNIT. MULTIPLE POWER SOURCES BE PRESENT, FAILURE
TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY
OR DEATH.
DO NOT SERVICE THIS UNIT WITHOUT FIRST SHUTTING OFF THE
POWER TO THE UNIT FROM THE CIRCUIT BREAKER AND/OR
REMOVING THE UNIT CORD SET PLUG FROM THE WALL OUTLET.
WARNING
THIS AIR CONDITIONER IS NOT MEANT TO PROVIDE
UNATTENDED COOLING OR LIFE SUPPORT FOR PERSONS
OR ANIMALS WHO ARE UNABLE REACT TO THE FAILURE OF
THIS PRODUCT.
THE FAILURE OF AN UNATTENDED AIR CONDITIONER MAY
RESULT IN EXTREME HEAT IN THE CONDITIONED SPACE
CAUSING OVERHEATING OR DEATH OF PERSONS OR
ANIMALS.
Operating
Voltage
Rating
230
/
208
265
Unit
Voltage
Minimum
197
238
Voltage
Utilization
Range
Maximum
253
292
Chart 3
-
Operating
Voltage
-7-
RED
-
24VAC
Purple
-
LS
control
Green
-
High
fan
speed
Blue
-
Reversing
valve
Yellow
-
Compressor
White
-
Heater
Orange
-
Low
fan
speed
Black
-
Common
ground
R
LS
GH
B
Y
W
GL
C
R
LS
GH
B
Y
W
GL
C
WALL
MOUNTED
THERMOSTAT
INTERFACE
Thermostat
WARNING
TO AVOID THE RISK OF PROPERTY DAMAGE, PERSONAL
INJURY OR
,
USE ONLY COPPER CONDUCTORS.
FIRE
WARNING
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH DUE TO ELECTRICAL SHOCK, DO NOT USE AN
EXTENSION CORD WITH THIS UNIT.
WARNING
TO AVOID THE RISK OF PROPERTY DAMAGE, PERSONAL
INJURY OR FIRE
DO NOT INSTALL WITH POWER CORD
STRETCHED OR UNDER A STRAIN AS THIS MAY CREATE
LOOSE PLUG/RECEPTACLE CONNECTION.
WARNING
TO AVOID THE RISK OF PERSONAL INJURY, WIRING TO THE
UNIT MUST BE PROPERLY POLARIZED AND GROUNDED.
Fig
9
wall
mounted
thermostat wiring
Fig 8 Receptacles
/
Sub
-
bases
NOTE: See the “
"
before
use the thermostat.
Remote
Thermostat
Change instructions
Tandem
230
/
208V
15Amp
265V
15Amp
Perpendicular
230
/
208V
20
Amp
265V
20
Amp
Large
tandem
230
/
208V
30Amp
265V
30Amp