68
NOTICE!
AVIS!
The inverter contains no components that are user serviceable.
10
Removal, transport, storage, disposal
Danger of death or severe injuries from dangerous voltage
►
Disconnect the inverter from the AC grid before removing
the AC conductors.
►
Verify absence of AC voltage before removing conductors.
Danger of death or severe injuries from dangerous voltage
Dangerous voltages can be present at the DC connections of the
inverter.
►
Never disconnect the PV modules when the inverter is con-
nected to AC grid or DC disconnect is on. First switch off the AC
conductors grid so that the inverter cannot feed energy into the
grid. Then, open the DC disconnect.
►
Verify absence of DC voltage before removing conductors.
Danger of injury due to heavy weight
The inverter is heavy (see “11. Techical Data”, p. 71). Incorrect
handling can lead to injuries.
►
The inverter must be lifted and carried by two people.
DANGER!
DANGER!
DANGER!
DANGER!
WARNING!
AVERTISSEMENT!
10.1
Removal
1. Switch off the AC breaker and verify absense of AC voltage.
2. Open the DC disconnect, verify the absense of DC voltage on both the inverter
and array sides, then disconnect PV array.
3. Remove DC and AC conductors and conduits from the inverter.
4. Unscrew the inverter from the wall bracket.
5. Lift the inverter from the wall bracket.
10.2
Packaging
Use the original packaging or packaging of the same quality.
10.3
Transport
Always transport the inverter in the original packaging or packaging of the same quality.