42
5.2.3
Keypad
Symbol
Use
ESC
•
Exit the current menu
•
Cancel the setting of a value
•
Move upwards in a menu
•
Set a value (increase the value)
•
Move downwards in a menu
•
Set a value (decrease the value)
•
Select a menu entry
•
Open a configurable value for editing
•
Finish editing (adopt the set value)
The menus have up to three levels:
[Main menu]
...
400 Production info
410 Current data
411 Current overview
412 Current data AC
...
420 Day statistics
430 Week statistics
...
500 User settings
Most menu names consist of a three-digit number and a menu title.
See “12.3 Overview of menu structure” for an overview of the complete menu structure.
5.2.4
General menu structure
1. Turn on the DC disconnect (put in closed position).
2. Check for inverter initialization; all 3 LED indicators are illuminated.
3. Turn on the dedicated 2-pole 240 Vac / 208 Vac circuit breaker in the building
electrical service panel (put in closed position).
4. Turn on the AC disconnect (put in closed position).
5. Refer to section 5 for setup process that needs to be completed before the
inverter can begin feeding power to the grid.
5.3
Inverter turn-on procedure