Mounting the inverter
Please make sure the inverter is installed vertically, especially if it is installed outdoors.
Figure 13: Inverter clearances
The National Electric Code may require significant larger working clearances (see NEC Section
110.26)
Inverter should be mounted
at least 39“ (100 cm) from
the floor or ground surface.
>6"
(15.2 cm)
>6"
(15.2 cm)
>4"
(10 cm)
>39"
(100 cm)
>20"
(50.8 cm)
Inverter should be at least
20“ (50.8 cm) from any
ceiling surface