Installation and Operation Manual (Rev B)
35
To view the date and time:
1. First select
Config
on the Main Menu then press
ENTER
.
2. Select the
Date/Time
option on the
Config
Menu then press
ENTER
.
3. The current date will be displayed.
Note:
The date is only editable if SRV Mode is off. When SRV Mode is on, the date
and time is automatically set.
4. Press the
ENTER
button to begin changing the date. The month will flash, indicating that this
portion of the date can be changed with the buttons. Press the
UP
button to increment the
month and the
DOWN
button to decrement the month. Press the
ENTER
button to accept the
month. Press the
ESCAPE
button to cancel and return to the menu. Days and years can be set
in a similar manner.
5. Press the ENTER button to begin changing the time. The format is HH:MM:SS and hours are
shown in 24 hour format. The hour will flash, indicating that this portion of the time can be
changed with the buttons. Press the
UP
button to increment the hour and the
DOWN
button
to decrement the hour. Press the
ENTER
button to accept the hour value. Press the
ESCAPE
button to cancel and return to the menu. Minutes and Seconds can be set in a similar manner.
7.10 Rebooting the SolrenView Gateway
If the SolrenView Gateway cannot communicate over the Internet or is not updating inverter data
it may need to be rebooted. To reboot SolrenView gateway:
1. First select
Config
on the
Main Menu
then press
ENTER
.
2. Select the
Reboot
option from the menu and press
ENTER
.
3. The Reboot monitor prompt will be shown. Press the
ENTER
button to reboot the SolrenView
gateway.
7.11 Resetting the SolrenView Gateway to Factory Defaults
It may be necessary to reset the SolrenView gateway to factory defaults. This does not reset the
inverter core, nor shutdown the inverter for any period of time.
NOTE:
Resetting the SolrenView gateway will also clear events, revenue-grade KYZ
counters and SolrenView.com data queue. Caution should be used with this
function to avoid data loss.
Содержание PVI 14TL
Страница 58: ...Installation and Operation Manual Rev B 58 ...