© CASWA Pty Ltd – 2014
14 | Page
This screen contains the two configurable RS485
fields and also shows the resulting string being
sent via the RS485 interface.
Define the required RS485 serial format in the
'
Format
' field incorporating the required loads
using the following codes:
%o = first load in tonnes
%O = first load in kilograms
%t = second load in tonnes %T = second load in tonnes
%r = carriage return
%n = line feed
Preceding or succeeding text can also be added. Note that to incorporate a percentage character,
you need to enter two %% characters.
The resulting string is visible in the 'Sending' field.
It is also important to define the communication speed by selecting the speed from the 'Baud'
selection box. This must match the speed set on the device that will be using the RS485 information.
5
ROUTINE MAINTENANCE
There is no routine maintenance for this device.
6
TROUBLESHOOTING
Fault
Cause
Fix
Unable to connect to
GateWay unit from FSU
GateWay or FSU are
busy
Power cycle the crane.
Incorrect wiring
Check that wiring is as per section 3.2.
Check that removable terminals have been reinserted
into their correct positions as shown in Figure 2.
Pluggable
terminals
not seating correctly.
Replace pluggable terminal and rewire the associated
terminals.
The GateWay is reporting
no load from a remote
device
Remote Device is not
communicating
Power cycle remote device then power cycle the
HoistNet Gateway
GateWay not connecting
to remote device
Remote device not
responding
to
connection request
Power cycle both devices