6 Install electric heating element
6 Install electric heating element
6.1 Important information
!
CAUTION
–
Follow the following installation steps
exactly.
–
If errors are made during installation,
the electric heating element's safety
devices will be ineffective.
–
The risk of subsequent damage is very
high.
–
The electric heating element, which is available
as an optional accessory
[1]
, is connected to the
primary circuit flow of the condenser (heat exchan-
ger).
–
A contactor and overtemperature reset (OTR) are
already preinstalled in the heat pump. CAUTION:
The capillary tube sensor of the overtemperature
reset must be positioned in the heating element
on site
–
The overtemperature reset protects the heating
element from overheating (by interrupting the
power supply, e.g. during dry running).
–
A mounting bracket is enclosed with the heating
element.
[1] The heating element is only available for the three-phase ver-
sion of the
vamp
air
, i.e. K 08.3, K 10.3, ...
!
CAUTION
- Protect the electrical terminal
area ofthe heat pump against moisture (e.g.
precipitation) during installation work.
6.2 Heating element and components
Overview: Heating element and components
Abb. 2-18
1 Electric heating element
2 Bracket
3 Temperature sensor T1 for condenser
4 Capillary tube sensor of the OTR
5 Contactor
6 Overtemperature reset (OTR)
Installation manual
vampair
19
Содержание Vampair
Страница 31: ...8 Electrical connection Installation manual vampair 31 8 5 Electrical connection plan ...
Страница 39: ...10 Foundation plan Installation manual vampair 39 Side view of foundation Section A A Abb 2 48 ...
Страница 44: ...Front view of foundation Section B B Abb 2 55 11 Flat roof set up 44 Installation manual vampair ...
Страница 51: ...12 Plant schematic Installation manual vampair 51 ...