Figure 11: StorEdge Connection Unit with and without internal cover
Backed-up Loads AC Breaker
: Main AC breaker for the backed-up loads. Ensure this
breaker is UP before starting up the system.
AC Bypass Switch
: This switch bypasses the inverter functionality in case of inverter
malfunction. Maintaining power to the backed-up loads is enabled by connecting
the loads directly to the grid.
There are three switch positions. The following table describes the functionality and
use of each position:
Switch
position
Use Case
Functionality
1 (left)
(Default)
Normal
operation
Normal operation.
The backed-up loads panel is connected through the
software controlled switches to the AC grid (during
normal operation), or to the inverter (via auto-
transformer, for backup power).
2 (right)
AC bypass
This mode disables the backup functionality.
The backed-up loads panel is connected directly to the
AC grid through the bypass switch. Use in case of
inverter malfunction.
0
Not in use
Mounting the Inverter
The inverter is supplied with a mounting bracket.
Figure 12: Mounting bracket
NOTE
Make sure the mounting surface or structure can support the weight of the
inverter and bracket, and make sure that it spans the width of the bracket.
Chapter 3: Installing the Inverter
35
StorEdge Solution with Backup MAN-01-00262-1.5
Содержание StorEdge Solution with Backup
Страница 1: ...Installation Guide StorEdge Solution with Backup For North America Version 1 5...
Страница 40: ...Figure 15 Inverter Covers Chapter 3 Installing the Inverter 39 StorEdge Solution with Backup MAN 01 00262 1 5...
Страница 98: ...Chapter 9 Setting Up Communication to the Monitoring Platform 97 StorEdge Solution with Backup MAN 01 00262 1 5...
Страница 101: ...Figure 34 Internal connectors StorEdge Solution with Backup MAN 01 00262 1 5 100 Communication Connectors...
Страница 141: ...Figure 47 The battery holder StorEdge Solution with Backup MAN 01 00262 1 5 140 9V Battery Replacement...