Power Optimizer Troubleshooting
If the inverter status screen indicates that not all power optimizers are paired or not all
are reporting (P_OK xxx/yyy, and x<y), those optimizers can be identified through the
LCD. Refer to
https://www.solaredge.us/sites/default/files/non_reporting_power_
Problem
Possible cause and troubleshooting
Pairing failed
Power optimizers are shaded.
If you connected the inverter to the SolarEdge monitoring
platform, retry pairing remotely (during sunlight). Make sure
to leave the inverter ON/OFF switch ON and that S_OK
appears in the status screen.
String voltage is 0V
Power optimizer(s) output is disconnected.
Connect all power optimizer outputs
String voltage not 0V but lower than 4V
Power optimizer(s) not connected in the string.
Connect all power optimizers
Module(s) not connected properly to power optimizer inputs
(not applicable to smart modules).
Connect the modules to the optimizer inputs
String reverse polarity.
Check string polarity using a voltmeter and correct if needed.
String voltage is higher than 4V
WARNING!
If the measured voltage is too high, the
installation may not have a safe low voltage.
PROCEED WITH CARE! A deviation of ±1% per
string is reasonable.
Si la tension mesuree est trop haute, la tension
basse de securite pourrait manquer dans
l’installation. REDOUBLEZ DE PRECAUTION.
Une deviation de ±1% par string est raisonnable.
Extra power optimizer(s) connected in the string (not
applicable to smart modules).
Check if an extra power optimizer is connected in the string.
If not – proceed to next solution.
A module is connected directly to the string, without a power
optimizer (not applicable to smart modules).
Verify that only power optimizers are connected in the string
and that no module outputs are connected without a power
optimizer. If the problem persists, proceed to the next step.
Power optimizer(s) malfunction.
o
Disconnect the wires connecting the power optimizers in
the string.
o
Measure the output voltage of each power optimizer to
locate the power optimizer that does not output 1V safety
voltage. If a malfunctioning power optimizer is located,
check its connections, polarity, module, and voltage.
o
Contact SolarEdge Support. Do not continue before
finding the problem and replacing the malfunctioning
power optimizer. If a malfunction cannot be bypassed or
resolved, skip the malfunctioning power optimizer, thus
connecting a shorter string.