LED
#
LED
Function
Indication
1
Bottom -
green
Operational
status
Flashing ON/OFF - normal
operation
2
Middle -
yellow
RS485 Modbus
communication
Flashing ON/OFF -
communication OK
3
Top -
yellow
Energy
management
Turns ON when the meter
reads an energy change of
~1 kwH. Then turns OFF.
DIP Switches
ID DIP Switches
The ID DIP switches are used to set the Modbus address of the
meter. The addressing options are listed in the table below. See
the figure
ID and Termination DIP Switches on page 18 for
switch direction guidelines.
Modbus Address
ID 1
ID 2
ID 3
0
Down
Down
Down
1
Up
Down
Down
2
Down
Up
Down
3
Up
Up
Down
4
Down
Down
Up
5
Up
Down
Up
6
Down
Up
Up
7
Up
Up
Up
Revenue Grade Energy Meter with Modbus Connection Installation Guide MAN-01-00609-1.0
Chapter 1: Introduction
17