UPS for 480 Vac Grid, User Guide, doc. rel.4.0
10.
(Appendix) Holding Registers for Modbus Queries
These registers can be addressed as either holding registers [for example,
4x0002] or input registers [for example, 3x0002])
Table 7: Holding Registers for Modbus queries
Register
Variable name
GET Values
Remarks
1
4x0001
Battery Condition
0: Good
1: Weak
2: Replace
2
4x0002
Battery Status
0: Battery OK
1: Battery Low
2: Battery
Depleted
Has effect only during power failure (battery
discharge), "Battery low" usually comes
minutes before the UPS batteries are depleted
and it switches off
3
4x0003
Battery Charge
0: Floating
1: Charging
2: Resting
3: Discharging
Most common situation is "floating" as a
constant state, however this depends on the
UPS topology
4
4x0004
Seconds On Battery
seconds
Has effect only during power failure
5
4x0005
Estimated Minutes
minutes
Mathematical estimation of available backup
time
6
4x0006
Estimated Charge
0-100%
Mathematical estimation of battery charge in
percent
7
4x0007
Battery Voltage
×10 Vdc
Divide the value by 10 for real measurement:
485/10=48.5 Vdc
8
4x0008
Battery Current
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
9
4x0009
Battery Temperature
°C
Degrees centigrade
11
4x0011
Input Lines Number
1 to 3
Number of the UPS input phases
12
4x0012
Input Frequency Line 1
×10 Hz
Divide the value by 10 for real measurement:
502/10=50.2 Hz
13
4x0013
Input Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
14
4x0014
Input Current Line 1
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
16
4x0016
Input Frequency Line 2
×10 Hz
Divide the value by 10 for real measurement:
502/10=50.2 Hz
17
4x0017
Input Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
18
4x0018
Input Current Line 2
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
20
4x0020
Input Frequency Line 3
×10 Hz
Divide the value by 10 for real measurement:
502/10=50.2 Hz