37
December 2020
|
Solar Stik
®
, Inc.
SYSTEM SETUP AND OPERATION GUIDE FOR THE SOLAR STIK USAF G-BOSS MEDIUM AND HEAVY HYBRID POWER SYSTEM
PRELIMINARY DRAFT
f Connect PRO-Verter 5000 to 120 VAC Loads (Optional)
Connect 120 VAC loads to the PRO-Verter AC outputs on the right side of the PRO-Verter. Connect
loads of no more than 20 amps for one (1) outlet and no more than 25 amps total between the two (2)
outlets. Turn off load power switches to prevent power draw during System setup.
Figure 24. PRO-Verter 5000 AC power output ports
120 VAC/20 A
Note:
The PRO-Verter inverter may be “turned off” during programming at Solar Stik (per
customer request). The PRO-Verter will not support AC loads when the inverter is turned off.
The inverter may be turned on following the instructions below:
1. Push the SETUP button on the PRO-Verter user interface.
2. Scroll to 02 Inverter Setup and press the rotary dial.
3. Scroll to 02F Power Up Always OFF and press the rotary dial.
4. Scroll to change 02F Power Up Always ON and press the rotary dial.
120 VAC/30 A
PRO-Verter
right-side view