1
December 2022
Solar Stik
®
, Inc.
TROUBLESHOOTING GUIDE
FOR THE
PRO-VERTER 5000-220 AFF1
DARI GATE SYSTEMS
Version 1.0 Updated:20221207
DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited.
Item # 20-XXXXXX
Страница 1: ...22 Solar Stik Inc TROUBLESHOOTING GUIDE FOR THE PRO VERTER 5000 220 AFF1 DARI GATE SYSTEMS Version 1 0 Updated 20221207 DISTRIBUTION STATEMENT A Approved for public release distribution is unlimited I...
Страница 2: ...harged to a critical low level the System may cease to function There are two 2 methods to restore a System with overdischarged batteries 1 Connect an active 230 VAC power source to the PRO Verter Gen...
Страница 3: ...d the alarm in PRO Verter will now beep steady If the Battery low voltage fault condition is not reset within the LV Cut Off Time the PRO Verter will shut down completely after the LV Cut Off Time LCD...
Страница 4: ...ng Current Pass through Current to the load is 1 A more than the set threshold of Grid Max Current Gen Max Current for 5 seconds current is sampled every 33 3 s There will be no AC output because the...
Страница 5: ...ll require manual reset by powering off waiting for 1 minute and then powering on again Note If there is short circuit condition in Charge mode i e when AC input is available short circuit condition o...