24VDC PRO-Verter 5000-120 AGS Operator Manual
Theory of Operation
Models of Operation
Depending on the application, there are several operational models that can be configured using a
PRO-Verter:
DC-only/Inverter (automatic functions)
Operating conditions – All power generated is from DC generators and AC loads are supported by
the PRO-Verter’s Inverter function using energy stored in batteries.
Hybrid (automatic functions)
Operating conditions – The “Continuous Load” AC power requirement is LESS than the individual
Inverter or Generator/Grid AC power output ratings.
In the Hybrid model, the PRO-Verter serves as the primary power management device in a System,
using either Inverter AC power or Generator/Grid AC power to maintain the load. In the Hybrid
model, the batteries will cycle regularly to mitigate generator run-time and logistical support often
associated with operation in remote locations. Hybrid systems also provide the operator with a
flexible architecture that allows for the addition of multiple power sources, such as renewable power
generation.
Load Support (automatic functions)
Operating conditions – The “Surge Load” AC requirement is MORE than the Generator/Grid AC
output, but less than the Inverter AC output rating.
In the Load Support model, the Load Support model allows the use of a smaller generator based
on total loads operating over 24 hour period rather than a larger generator that is required for
the “peak” loads, which may only last for a brief period. The PRO-Verter can be used to provide
supplemental “surge” AC power to a generator/grid AC source during brief/intermittent periods
while allowing the “continuous” loads to be supported in the Hybrid model.
Peak Power Delivery (manual functions)
Operating conditions – The “Peak Load” AC requirement is MORE than the PRO-Verter AC
continuous output ratings.
In the Peak Power Delivery model, the PRO-Verter combines generator/grid AC power with Inverter
AC power to support “peak” AC for brief periods. This mode can only be supported for limited
durations and is directly dependent on the total battery capacity and their SOC.