Connections

Top

                                                           Bottom 

For further information on connecting the ripple control receiver, please refer 
to the installation manual.

Quick Start Guide

MOD I/O

Introduction

           This installation manual is intended for use by solar energy technicians and  
           professional electricians, as well as Solar-Log Base users. It should be noted 
that the installation and commissioning of the individual components is only to be 
performed by properly trained specialists. 

The Solar-Log™ must only be used by persons who have fully read and under-
stood this manual before installing, operating and/or servicing the device.

Please observe!

           Disconnect the power of the Solar-Log Base before plugging in/out the bus 
           connector and before connecting the module with the Solar-Log™.

Assembly

The MOD I/O module is manufactured in accordance with protection class IP20 
and is designed exclusively for installation in suitable for dry, dust-free indoor use. 
The assembly itself can be carried out both via wall mounting as well as on a DIN 
rail. Power is supplied via the bus system by the Solar-Log Base, a power supply 
via pins power + and - is not required for the PM+ function. The need of an exter-
nal power supply is optional and depends on the output current.

Module MOD I/O connection and mounting

Take one of the 2 bus connectors included in the scope of delivery. The bus con-
nector is plugged into the back of the Solar-Log Base.

Take the second bus connector and plug it into the back of the MOD I/O.
To complete the HBus connection, plug the two bus connectors together. 
Now the connected housings can be snapped into the DIN rail.

Follow the short instructions Solar-Log Base.

Technical Data

Device voltage

24V (+-5 %), in exceptional cases 12V (+-5 %)   

Total current of the outputs With a power supply via the HBus: 250 mA

With an external power supply: 1A

Cable cross-section

Solid conductor: 0.2 … 1.5 mm² / 24 … 16 AWG

Fine-stranded conductor: 0.2 … 1.5 mm² / 24 … 16 AWG 

With ferrules: 0.14 ... 1 mm²/ 26 ... 18 AWG (ferrules 

– to be used for fi ne-stranded conductor)

Strip length

8.5 … 9.5 mm / 0.33 … 0.37 inch, with ferrules 

 6mm / 0,24 inch

Please take into account the diameter of the plastic sleeves

Power consumption

min. 2 W

Control signal

Voltage of the control signal corresponds to

Supply voltage of the Solar-Log Base

Dimensions (Wx-

HxD) in mm

53,6x89,7x60,3

Solare Datensysteme GmbH • www.solar-log.com • Subject to change without notice • EN | 11.2020 | Version 1.4 | Art.Nr.: 15818

Pin

MOD I/O

COM Functional earthing

1

Control signal active power 

2

Digital_In 1

3

Digital_In 2

4

Digital_In 3

5

Digital_In 4

6

Control signal reactive power 

COM Functional earthing

Currently without function

Power

6

5 4

3

2

1

Without function

PM+

COM

COM

-

+