43
Operating via a web browser within your own network
Consumption (kW):
This value is calculated from the consumption meters and refers to the entire plant. The values displayed
in the respective bus column only refer to the plant total and are not taken into account in the correspond-
ing columns. The consumption value is normally subtracted from the allowed power from the entire plant.
Control value power (kW):
This value is calculated by the Solar-Log™ and is the maximum current power output from the inverters. It
is used for the current target power output.
Note:
The values recorded may differ due to rounding in the calculations by the Solar-Log™ (technical reasons).
Current power output (kW):
The value refers to the current output generated by the inverter per interface (column) and for the entire
plant.
Control value power (% AC):
The Solar-Log™ calculates the control value power (kW) as a percentage of the maximum AC power and
relays this to the inverters.
Current power output (AC%):
The value indicates the total output generated as a percentage of the maximum AC power for the inverter
or all of the inverters on a bus.
Feed-in power (% DC):
This value is the current amount of feed-in power as a percentage of the generated output.
Explanation of the Symbols in the Feed-in power (% DC) column:
The feed-in power value is in the target power range with a tolerance of -2% to +1%.
The feed-in power value is below the target value allowed. Generally, this means that the out-
put allowed at the grid connection point is not being achieved due to low irradiation or high
self-consumption.
This means that the value is above the target value allowed.
If the red triangle is only displayed at a bus and entire plant has a green symbol, this means
that only this bus is over the target value allowed. However, the plant totals do not go over the
target value because of self-consumption.