October 26
th
, 2022 42
The Batt % meter is not reaching 100%
•
The system needs to go through a small discharge/charge cycle first to calibrate the battery
Generator setup is reading 0Hz
•
Select "General Standard" instead of UL1741. Then widen the frequency range to 55Hz-65Hz.
Color Touchscreen is Frozen
•
Press and hold the escape button [
] for 7-10 seconds
Troubleshooting Phasing Issues
If the Sol-Ark screen shows
Grid Phase Wrong
there is a phasing issue with your wiring and it may cause overload faults
(F18, F26, F34) even with the Load breaker
off
and
WILL CAUSE DAMAGE if left unchecked
.
Single Sol-Ark: To locate the improperly wired phases, measure
L1
to
L1 (Top Screws)
between the
Grid
and
Load
breaker; you should see 0V AC. Repeat for
L2
to
L2
between the
Grid
and
Load
breaker. Attempt to correct the wiring
until you are only reading 0V AC between
L1
to
L1
&
L2
to
L2
.
Make sure to correct both the Grid and Load wiring; they both need to be correct.
If the error persists, you will need to check your AC wiring beyond the inverter and may also need to verify that the
phases are properly labeled coming from your meter.
Sol-Ark 8K Error Codes
Fault
Instruction
Common Cause/Remedy
F1
DC Inversed Failure
If you have parallel systems and turn one system off, you with get this notification. Not a fault.
F8
GFDI_Relay_Failure
Current Leakage from inverter AC output to Ground, check Ground and neutral are connected at the main
panel
F13
Grid_Mode_change
It can happen when not using batteries or if Grid Input settings are changed. This is a notification, NOT a
fault. If you switch from No Batt to Battery mode, Power the System down completely to restart.
F15
AC_OverCurr_Failure
It is usually caused by Loads too large for the inverter. If off-grid, the battery discharge amps are
programmed too low. Overloads can result in F15, F18, F20, or F26.
F16
GFCI_Failure
Ground fault. Check PV+ or PV- wiring (which must be ungrounded). Exposed PV cond rain can also
cause. Check that the neutral line and Ground are not double-bonded (common with portable generators).
F18
Tz_Ac_OverCurr_Fault
Overloaded the Load Output: reduce loads. Wiring Short on the AC Side can also cause this error. Overloads
can result in F15, F18, F20, or F26.
F20
Tz_Dc_OverCurr_Fault
It is typically caused by DC current from the battery that is too large (ex: 4 Ton AC Unit). Overloads can
result in F15, F18, F20, or F26.
F22
Tz_EmergStop_Fault
Initiated Emergency Stop; see sensor pinout table.
F23
Tz_GFCI_OC_Fault
PV Ground fault. Check PV+ or PV- wiring (which must be ungrounded or damage can occur). Typically
caused by pinched PV wire grounding the PV+ or PV-. Grounded PV wire can cause F20, F23, or F26.
Содержание 8K-2P-N
Страница 5: ...October 26th 2022 5 Spec Sheet ...
Страница 9: ...October 26th 2022 9 Diagram 2 Diagram 3 ...
Страница 10: ...October 26th 2022 10 Note PV fuses are only required for 2 strings per MPPT Diagram 4 ...
Страница 12: ...October 26th 2022 12 GUI Screens Main Menus Basic Setup ...
Страница 13: ...October 26th 2022 13 c Battery Setup Grid Setup ...