![Softing echolink one2PROFINET Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/softing/echolink-one2profinet/echolink-one2profinet_instruction-manual_1312387046.webp)
15.1.15
echolink one2PROFINET V. 1.0
46
Softing Industrial Automation GmbH
Error handling
10 Error handling
10.1 Error handling at echolink one
If the Gateway detects an error, the error is signalled by the “State“ LED lighting red and, simulta-
neously, the error number being indicated by means of LEDs “Error No.“ as shown in the table
below (Flashing frequency 1 Hertz). A distinction can be made between two error categories:
Serious errors (1-5): In this case, the Gateway must be switched off and switched back on again.
If the error occurs again, the Gateway must be exchanged and returned for repair.
Warnings (6-15): These warnings are displayed for one minute simply for information purposes
and are then automatically reset. If such warnings occur frequently, please inform After-Sales
Service.
In the configuration mode these displays are not valid and only meant for internal use.
LED8 LED4 LED2 LED1
Error no.
resp. ID
Error description
0
0
0
0
0
Reserved
0
0
0
1
1
Hardware fault
0
0
1
0
2
EEROM error
0
0
1
1
3
Internal memory error
0
1
0
0
4
Fieldbus hardware error
0
1
0
1
5
Script error
0
1
1
0
6
Reserved
0
1
1
1
7
RS-transmit buffer overflow
1
0
0
0
8
RS-receive buffer overflow
1
0
0
1
9
RS timeout
1
0
1
0
10
General fieldbus error
1
0
1
1
11
Parity-or frame-check-error
1
1
0
0
12
Reserved
1
1
0
1
13
Fieldbus configuration error
1
1
1
0
14
Fieldbus data buffer overflow
1
1
1
1
15
Reserved
Table 1: Error handling at echolink one - system errors.
Содержание echolink one2PROFINET
Страница 41: ...Implemented protocols in echolink one Softing Industrial Automation GmbH 41 echolink one2PROFINET V 1 0 15 1 15...
Страница 57: ...Appendix Softing Industrial Automation GmbH 57 echolink one2PROFINET V 1 0 15 1 15...
Страница 58: ...15 1 15 echolink one2PROFINET V 1 0 58 Softing Industrial Automation GmbH Appendix...
Страница 59: ...Appendix Softing Industrial Automation GmbH 59 echolink one2PROFINET V 1 0 15 1 15...