7.2. Maintenance
Inverters generally do not need any daily or routine maintenance. But ensure heat
sink should not be blocked by dust, dirt or any other items. Before the cleaning,
make sure that the DC SWITCH is turned OFF and the circuit breaker between
inverter and electrical grid is turned OFF. Wait at least for 5 minutes before the
Cleaning.
Inverter cleaning
Please clean the inverter with an air blower, a dry & soft cloth or a soft bristle
brush. Do NOT clean the inverter with water, corrosive chemicals, detergent, etc.
Heat sink cleaning
For the long-term proper operation of inverters, ensure there is enough space
around the heat sink for ventilation, check the heat sink for blockage (dust, snow,
etc.) and clean them if they exist. Please clean the heat sink with an air blower, a
dry & soft cloth or a soft bristle brush. Do NOT clean the heat sink with water,
corrosive chemicals, detergent, etc.
Fan cleaning
For inverter SOFAR 25~50KTLX-G3 with fans, please check if inverter have
abnormal sound when inverter is operating. Check if fan on cracks, replace a new
fan when necessary. Refers to below section.
7.3. Fan Maintenance
For SOFAR 25~50KTLX-G3 series inverter with fans, if fan is broken or not working
properly may cause inverter heat dissipation issue and effect the working efficiency
of inverter. Thus, fans need to have regularly cleaning and maintain, details
operating as below:
Step 1:
Closed inverter, check the wiring side to ensure all electrical connection of
inverter is turn off ;
Step 2:
Unscrew six screws at the corner of fans baseboard ;