background image

www.socomec.com

SIDER

Visible breaking Switch

EN

 

Instr

uctIon

 

Manual

Содержание SIDER

Страница 1: ...www socomec com SIDER Visible breaking Switch EN Instruction Manual ...

Страница 2: ... accessory 6 2 4 2 Factory fitted accessory 6 3 INSTALLATION 7 3 1 Product dimensions 7 3 2 Copper bar connection for SIDER from 2000 to 3200 A 7 3 3 Mounting orientation 8 3 4 Assembly of customer mounted accessories 8 3 4 1 Connection kits for SIDER from 2000 to 3200 A 8 3 4 2 Terminal screens 9 3 5 Factory fitted accessory 10 3 5 1 Additional auxiliary contacts for B7 1250 to 1800 A optional 10...

Страница 3: ...ith this product may cause injury electric shock burns or death Prior to carry out any maintenance or other work on live parts or other parts in the vicinity of exposed live parts ensure that the switch including all control and associated circuits are de energized Installation and maintenance work on this device may only be carried out by an authorized electrician Every user or person standing in...

Страница 4: ...reak switch 3 poles 2 Load break switch terminals 3 Back plate mounting SIDER fixing lugs 4 Sliders for Terminal Shields 5 Fixing holes for terminal Shields 2 2 Product identification 1 1 Main switch identification label Electrical characteristics Applicable standards and Terminal incoming and outgoing wiring details ...

Страница 5: ...tor Temperature 0 9 40 C 50 C 0 8 50 C 60 C 0 7 60 C 70 C Simplified derating method Ithu Ith x Kf A more precise calculation may be done for specific applications Should this be required please contact SOCOMEC 2 3 2 2 Hygrometry 80 humidity without condensation at 55 C 95 humidity without condensation at 40 C 2 3 2 3 Altitude Up to 2000m in altitude without derating For higher altitude the Ka cor...

Страница 6: ...tromagnetic compatibility of technical equipment no TR CU 020 2011 dated 9th December 2011 Safety of low voltage equipment no TR CU 004 2011 dated 16th August 2011 14 9 22 9 EAC ai 100 80 2 3 6 Lead free process The SIDER complies with the European directive for RoHS 2 4 SIDER ACCESSORIES AVAILABLE 2 4 1 Customer fitted accessory TERMINAL SCREENS Incoming and outgoing protection against direct con...

Страница 7: ... 10 16 258 7 87 200 Fix 9 84 250 0 31 8 0 31 8 2 60 66 5 73 145 5 5 73 145 5 0 31 8 3 19 81 2 1 20 91 531 0 19 5 0 19 5 ø 0 49 ø 12 5 0 98 25 1 18 30 0 77 45 0 98 25 1 18 30 0 77 45 3 54 90 0 59 15 0 49 12 5 1 Terminal screens 2 Phase Barriers B7 1250 to 1800 A B8 2000 to 3200 A 3 2 Copper bar connection for SIDER from 2000 to 3200 A 2 91 74 1 46 37 5 08 129 6 10 155 2 91 74 1 46 37 5 08 129 6 10 ...

Страница 8: ...2500 A 2500 A 2 x 100 x 10 H M12 35 6 8 6 x 12 x 6 x 02 2000 A 2500 A 2500 A 2 x 100 x 10 H M12 55 6 8 3 x 6 x 3 x 03 2000 A 2500 A 2500 A 2 x 100 x 10 H M12 55 6 8 5 x 10 x 5 x 04 2000 A 2500 A 3200 A 3 x 100 x 10 H M12 35 6 8 3 x 3 x 05 2000 A 2500 A 3200 A 3 x 100 x 10 H M12 45 6 8 3 x 6 x 06 2000 A 2500 A 2900 A 3 x 100 x 10 H M12 65 6 8 3 x 6 x 3 x 07 2000 A 2500 A 3200 A 4 x 100 x 10 H M12 4...

Страница 9: ...9 EN SIDER 546 418 A SOCOMEC 3 4 2 Terminal screens Top Bottom B7 1250 to 1800 A ref 1509 3160 Top Bottom B8 2000 to 3200 A ref 1509 3200 ...

Страница 10: ...1 O OFF 1 Pos I Intended for pre breaking and signaling of positions I Up to 2 additional NO NC auxiliary contacts can be fitted 3 5 2 Additional auxiliary contacts for B8 2000 to 3200 A standard 82 92 or 84 94 81 91 Pos I 81 81 82 84 91 92 94 Pos I Pos I 82 84 91 92 94 O OFF Intended for pre breaking and signaling of positions I Up to 2 additional NO NC auxiliary contacts can be fitted ...

Страница 11: ...4x100 x5 3x100 x10 Maximum cables section Cu mm2 4x185 6x185 Maximum bars width Cu mm 63 100 100 100 100 5 TROUBLE SHOOTING GUIDE It is not possible to manually operate the switch Make sure that the product is not padlocked Verify the rotation direction of the handle Apply a sufficient progressive action in the direction as indicated on the handle Impossible to padlock Verify that the SIDER is in ...

Страница 12: ...546 418 A EN 09 16 Non contractual document 2016 Socomec SAS All rights reserved CORPORATE HQ CONTACT SOCOMEC SAS 1 4 RUE DE WESTHOUSE 67235 BENFELD FRANCE www socomec com ...