43
EN
ATyS / ATyS r - 541630C - SOCOMEC
800 to 3200 A
ThermalcurrentI
th
at 40°C
800 A
1000 A
1250 A
1600 A
2000 A
2500 A
3200 A
Framesize
B6
B6
B6
B7
B8
B8
B8
Rated insulation voltage U
i
(V)(powercircuit)
1000
1000
1000
1000
1000
1000
1000
Rated impulse withstand voltage U
imp
(kV)(powercircuit)
12
12
12
12
12
12
12
Rated insulation voltage U
i
(V)(controlcircuit)
300
300
300
300
300
300
300
Rated impulse withstand voltage U
imp
(kV)(controlcircuit)
4
4
4
4
4
4
4
Rated operational currents I
e
(A) according to IEC 60947-3
Ratedvoltage
Utilisationcategory
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
A/B
(1)
415 VAC
AC-21 A / AC-21 B
800/800
1000/1000 1250/1250 1600/1600
-/2000
-/2500
-/3200
415 VAC
AC-22 A / AC-22 B
800/800
1000/1000 1250/1250 1600/1600
-/2000
-/2500
-/3200
415 VAC
AC-23 A / AC-23 B
800/800
1000/1000 1250/1250 1250/1250
-/1600
-/1600
-/1600
500 VAC
AC-21 A / AC-21 B
800/800
1000/1000 1250/1250 1600/1600
-/2000
-/2000
-/2000
500 VAC
AC-22 A / AC-22 B
630/630
800/800
1000/1000 1600/1600
500 VAC
AC-23 A / AC-23 B
630/630
630/630
800/800
1000/1000
690 VAC
(3)
AC-21 A / AC-21 B
800/800
1000/1000 1250/1250 1600/1600
-/2000
-/2000
-/2000
690 VAC
(3)
AC-22 A / AC-22 B
630/630
800/800
1000/1000 1000/1000
690 VAC
(3)
AC-23 A / AC-23 B
630/630
630/630
800/800
800/800
220VDC
DC-21A/DC-21B
800/800
1000/1000 1250/1250 1250/1250
220VDC
DC-22A/DC-22B
800/800
1000/1000 1250/1250 1250/1250
220VDC
DC-23A/DC-23B
800/800
1000/1000 1250/1250 1250/1250
440VDC
(2)
DC-21A/DC-21B
800/800
1000/1000 1250/1250 1250/1250
440VDC
(2)
DC-22A/DC-22B
800/800
1000/1000 1250/1250 1250/1250
440VDC
(2)
DC-23A/DC-23B
800/800
1000/1000 1250/1250 1250/1250
Rated operational currents I
e
(A) according to IEC 60947-6-1
Ratedvoltage
Utilisationcategory
415 VAC
AC-31 B
800
1000
1250
1600
2000
2500
3200
415 VAC
AC-32 B
800
1000
1250
1250
2000
2000
2000
415 VAC
AC-33 B
800
1000
1000
1000
1250
1250
1250
Current rated as conditional short-circuit with fuse gG DIN, according to IEC 60947-3
Prospectivefuseprotectedshort-circuitwithstandat415VAC(kArms)
50
50
100
100
Prospectivefuseprotectedshort-circuitwithstandat690VAC(kArms)
50
50
50
Associatedfuserating(A)
800
1000
1250
2x800
Short-circuit withstand without protection as per IEC 60947-3
Rated short-time withstand current 0.3s I
cw
at415VAC(kArms)
64
64
64
78
78
78
78
Rated short-time withstand current 1s I
cw
at415VAC(kArms)
35
35
35
50
50
50
50
Ratedpeakwithstandcurrentat415VAC(kApeak)
55
55
80
110
120
120
120
Short-circuit withstand without protection as per IEC 60947-6-1
Ratedshort-timewithstandcurrent30 msI
cw
at415VAC(kArms)
Ratedshort-timewithstandcurrent60 msI
cw
at415VAC(kArms)
20
20
25
32
50
50
50
Connection
MinimumCucablecross-sectionasperIEC60947-1(mm²)
2x185
RecommendedCubusbarcross-section(mm²)
2x50x5
2x63x5
2x60x7
2x100x5
3x100x5 2x100x10 3x100x10
MaximumCucablecross-section(mm²)
4x185
4x185
4x185
6x185
MaximumCubusbarwidth(mm)
63
63
63
100
100
100
100
Min./max.tighteningtorque(Nm)
9/13
9/13
20/26
40/45
40/45
40/45
40/45
Switching time (rated voltage, after receiving command)
TransfertimeI-IIorII-I(s)
2.8
2.8
2.8
2.9
2.8
2.8
2.8
I-0orII-0(s)
1.4
1.4
1.4
1.4
1.8
1.8
1.8
Contacttransfertime("black-out"I-II)minimum(s)
1.4
1.4
1.4
1.5
1
1
1
Power supply
Min./max.power(VAC)
166/332
166/332
166/332
166/332
166/332
166/332
166/332
Control supply power demand
Demand/ratedpower(VA)-ATySr,ATySd
460/184
460/184
460/184
460/230
812/322
812/322
812/322
Demand/ratedpower(VA)-ATySt,g,p
482/206
482/206
482/206
482/252
834/344
834/344
834/344
Mechanical specifications
Durability(numberofoperatingcycles)
4,000
4,000
4,000
3,000
3,000
3,000
3,000
WeightATySr3P/4P(kg)
27.9/ 32.2 28.4/ 32.9 28.9/ 33.6
33.1/ 39.4
50.7/ 61.6
50.7/ 61.6
61.0/ 75.3
WeightATySd3P/4P(kg)
28.5/ 32.8 29.0/ 33.5 29.5/ 34.2
33.7/ 40.0
51.3/ 62.2
51.3/ 62.2
61.6/ 75.9
WeightATySt,g,p3P/4P(kg)
29.0/ 33.3 29.5/ 34.0 30.0/ 34.7
34.2/ 40.5
51.8/ 62.7
51.8/ 62.7
62.1/ 76.4
(1) Category with index A = frequent operation - Category with index B = infrequent operation.
(2) 3-pole device with 2 pole in series for the “+” an 1 pole for the “-”.
4-pole device with 2 poles in series by polarity.
(3) Interphase barriers must be installed on the products.
(4) Values given at 690 VAC.
Содержание ATyS r
Страница 3: ...3 EN ATyS ATyS r 541630C SOCOMEC ...
Страница 26: ...26 EN ATyS ATyS r 541630C SOCOMEC 6 3 4 Terminal screens 125A to 630A 500A to 1600A 2000A to 3200A ...
Страница 41: ...41 EN ATyS ATyS r 541630C SOCOMEC 9 CHARACTERISTICS ...
Страница 51: ......