28
EN
ATyS / ATyS r - 541630C - SOCOMEC
6.3.6. Incoming copper bar connection kit assembly
2000A – 2500A (MINIMUM CU BAR SECTION FOR ITH 2000A 3X100X5MM; AND FOR ITH 2500A 4X100X5MM)
VERSION 01
VERSION 02
VERSION 03
Direct
Connection
V2 & V3
Kit :
26191200x1
26291200x1
26391200x1
3200A (MINIMUM CU BAR SECTION 3X100X10MM)
VERSION 04
VERSION 05
VERSION 06
A
B
A
B
!
2900AMax
Connection
bar 2619 1200
included with
3200A
V4
Kit :
26991200x1
V5 & V6
Kit :
26291200x1
26391200x1
6.3.7. Outgoing bridge connection assembly
2000A – 2500A (MINIMUM CU BAR SECTION FOR ITH 2000A 3X100X5MM; FOR ITH 2500A 4X100X5MM)
VERSION 07
VERSION 08
VERSION 09
V7 & V8
Kit :
26191200x2
26991201x2
26291200x1
41090320x1
V9
Kit :
26191200x2
26291200x2
26391200x2
3200A (MINIMUM CU BAR SECTION 3X100X10MM)
VERSION 10
VERSION 11
VERSION 12
!
2900AMax
Connection
bar 2619 1200
included with
3200A
V10 & V11
Kit :
26991201x2
26291200x1
41090320x1
V12
Kit :
26291200x2
26391200x2
Содержание ATyS r
Страница 3: ...3 EN ATyS ATyS r 541630C SOCOMEC ...
Страница 26: ...26 EN ATyS ATyS r 541630C SOCOMEC 6 3 4 Terminal screens 125A to 630A 500A to 1600A 2000A to 3200A ...
Страница 41: ...41 EN ATyS ATyS r 541630C SOCOMEC 9 CHARACTERISTICS ...
Страница 51: ......