7

overview

At the Socket Test stage the PDL 200A and PDL 234 also accurately
measures and displays the Mains Voltage on one of the 3 LED’s.

The voltage is banded to directly reflect the new Mains Supply
Harmonised Standards BS 7697 HD 42S1. 

The measurement result is

LOW

CORRECT

HIGH

less than 207 V AC

207-253 V AC

greater than 253V AC

If the Voltage Range is outside of this standard, stop testing - your customer 
should notify their electricity supply company of the problem.

The Front panel of the tester gives a short reminder of Correct
Socket Wiring (3 GREEN LED’s and continuous tone) and also
indicates 4 of the most common Socket Wiring problems (RED
LED(s) and warble alarm tone).

If the three socket LED’s are GREEN (correct) and the GREEN Mains
Voltage LED is illuminated (correct) you can proceed to Loop Test by
pressing the Loop Test Button.

Содержание PDL 200A Series

Страница 1: ...PDL 200A PDL 234 SERIES MULTIFUNCTION ELECTRICAL TESTERS Tests no trip loop socket mains voltage polarity PDLSERIES U S E R M A N U A L 0 6 0 6...

Страница 2: ...notes given on page 8 are for guidance only full reference to the IEE Wiring Regulations must be made l Before use check your tester for any damage to the plug leads and cabinet At Socket See our Eng...

Страница 3: ...extremely rare this miswire condition can exist so if your test shows this fault do not proceed if in any doubt advise your customer to contact their supply company immediately FUSE100A FUSE100A From...

Страница 4: ...0A and PDL 234 Loop Testers the tester will first go through a brief self check routine and then check that the socket is correctly wired by showing three green green for GO LED s with a continuous to...

Страница 5: ...so indicate sequence of test 5 overview 5 5 LED s show Loop Test result 2 Table of correct and common Socket Wiring faults 7 Polarity Test Indications 1 3 LED s show Socket Wiring status 3 3 LED s ind...

Страница 6: ...d Your tester is equipped with 2 methods of connecting to a socket or a spur This test lead is used for sockets WARNING you are strongly advised to switch off the MCB or disconnect the fuse feeding th...

Страница 7: ...r than 253V AC If the Voltage Range is outside of this standard stop testing your customer should notify their electricity supply company of the problem The Front panel of the tester gives a short rem...

Страница 8: ...o seee if it is just tarnished socket contacts or checking where the socket is located if it is the furthest point from the distribution board you may expect it to be a higher reading Less than 100 Oh...

Страница 9: ...est LED s should flash GREEN everything is correctly wired including Polarity live and earth neutral are in the right place If the LED s change to RED when you operate the Touch Pad it is possible a v...

Страница 10: ...incorrectly wired one or more LED s will go to FLASHING RED to indicate there is a a socket miss wire or other fault If flashing red or orange occurs using the touch pad at this stage this should sho...

Страница 11: ...displayed on 3 LED s 207V AC LOW 207 253V AC STANDARD 253V AC HIGH Loop Test Continuous reading loop resistance Rl Re with result displayed on 5 LED s Test current 15mA at 253V AC Range 1 2 20 200 200...

Страница 12: ...miswire L N E Warble 6 Faulty N L E miswire NC L N Warble 7 Faulty N E miswire NC N L Warble 8 Faulty N NC E L Warble 9 Faulty N L E reverse NC L E Warble 10 Faulty E L N reverse L NC N Warble 11 Fau...