background image

10

PDL Series

Socket Test Technology

The PDL 200A and PDL 234 use our well proven Socket Testing patented 
technology to indicate the socket is correctly wired.

Plugging the unit in and switching on mains supply automatically initiates the
socket test sequence.

If the socket is correctly wired the LED’s will be GREEN on this check.

If the socket is incorrectly wired one or more LED’s will go to FLASHING RED to
indicate there is a a socket miss-wire or other fault.

If flashing red (or orange) occurs using the touch pad at this stage, this should
show where the socket wiring problem is – as per the example below.

A unique feature of your tester is the ability to display by the position of the red
LED(s) where the problem is, EARTH, LIVE (Phase) or NEUTRAL.

A full list of wiring faults is shown on the back cover of this User Guide.

This is an example of ‘Fault Locate’ showing Live (Phase), neutral reverse.

Содержание PDL 200A Series

Страница 1: ...PDL 200A PDL 234 SERIES MULTIFUNCTION ELECTRICAL TESTERS Tests no trip loop socket mains voltage polarity PDLSERIES U S E R M A N U A L 0 6 0 6...

Страница 2: ...notes given on page 8 are for guidance only full reference to the IEE Wiring Regulations must be made l Before use check your tester for any damage to the plug leads and cabinet At Socket See our Eng...

Страница 3: ...extremely rare this miswire condition can exist so if your test shows this fault do not proceed if in any doubt advise your customer to contact their supply company immediately FUSE100A FUSE100A From...

Страница 4: ...0A and PDL 234 Loop Testers the tester will first go through a brief self check routine and then check that the socket is correctly wired by showing three green green for GO LED s with a continuous to...

Страница 5: ...so indicate sequence of test 5 overview 5 5 LED s show Loop Test result 2 Table of correct and common Socket Wiring faults 7 Polarity Test Indications 1 3 LED s show Socket Wiring status 3 3 LED s ind...

Страница 6: ...d Your tester is equipped with 2 methods of connecting to a socket or a spur This test lead is used for sockets WARNING you are strongly advised to switch off the MCB or disconnect the fuse feeding th...

Страница 7: ...r than 253V AC If the Voltage Range is outside of this standard stop testing your customer should notify their electricity supply company of the problem The Front panel of the tester gives a short rem...

Страница 8: ...o seee if it is just tarnished socket contacts or checking where the socket is located if it is the furthest point from the distribution board you may expect it to be a higher reading Less than 100 Oh...

Страница 9: ...est LED s should flash GREEN everything is correctly wired including Polarity live and earth neutral are in the right place If the LED s change to RED when you operate the Touch Pad it is possible a v...

Страница 10: ...incorrectly wired one or more LED s will go to FLASHING RED to indicate there is a a socket miss wire or other fault If flashing red or orange occurs using the touch pad at this stage this should sho...

Страница 11: ...displayed on 3 LED s 207V AC LOW 207 253V AC STANDARD 253V AC HIGH Loop Test Continuous reading loop resistance Rl Re with result displayed on 5 LED s Test current 15mA at 253V AC Range 1 2 20 200 200...

Страница 12: ...miswire L N E Warble 6 Faulty N L E miswire NC L N Warble 7 Faulty N E miswire NC N L Warble 8 Faulty N NC E L Warble 9 Faulty N L E reverse NC L E Warble 10 Faulty E L N reverse L NC N Warble 11 Fau...

Отзывы: