6.3

 

FCM magnetic stroke limit switches 

The magnetic stroke end switches FCM allow to limit the actuator stroke length avoiding to reach the extreme 
positions  (mechanical  stop)  and  preventing  damage.  Using  more  switches  it  is  also  possible  to  set 
intermediate positions along the actuator stroke length. 
The stroke end switches must be fixed on the external tube and are activated by a toroidal magnetic field 
independently of their angular position. 

The magnetic reed switches can work only if connected to a control circuit to activate electric relay. 
Do not connect the reed switches in series between the power supply and the electric motor. 

Actuators equipped  with  magnetic  stroke  end  switches  perform  a  linear  travel  shorter  than  their
stroke length code, because the reed switch FC 1 gives the stopping signal to the actuator before the
actuator has travelled the total stroke length. To know the actual stroke please refer to the product
catalogue or to the check sheet supplied with the actuator.

When using more contact reeds for intermediate positions, it shall be considered that the same reed
switch can give the signal in 2 different positions, depending on the actuator motion which can be
retracting or extending.

Figure 6.2 – FCM magnetic stroke limit switches

 

FCM magnetic limit switches are supplied already fixed on extreme stroke positions Lc and La (see Fig. 6.10): 

RETRACTED ACTUATOR (Lc) position: FC 1 reed switch fixed on the tube up to the actuator housing.

EXTENDED ACTUATOR (La) position: FC 2 reed switch fixed on the limit marked on the outer tube.

The position of the reed switches can be adjusted by changing the fixing clamp position on the tube: 

Release the screw on the fixing clamp (do not release the fixing screw of the reed sensor)

Move the fixing clamp on the tube to the desired position (do not exceed the maximum range Lc …
La)

Fix the screw of the clamp.

DO NOT SET THE FC 2 SWITCH POSITION OVER THE LIMIT MARK ON THE TUBE. 
DO NOT TRAVEL OVER THE STROKE LIMIT SWITCHES POSITIONS, AVOIDING TO REACH MECHANICAL 
STOP AND PREVENTING DAMAGE TO THE INTERNAL COMPONENTS OF THE ACTUATOR. 

Содержание ACL2 120

Страница 1: ...ON AND MAINTENANCEnance NO 01 210003 LINEAR ACTUATORS ACME SCREW ACL2 120 ACL2 125 ACL2 128 ACL2 130 ACL2 140 BALL SCREW ACL2 120B ACL2 125B ACL2 128B ACL2 130B ACL2 140B ENGLISH Ed 08 2021 02 20 25 2...

Страница 2: ...elieve SNT from any liability for damage caused to persons and or property SNT does not assume direct or indirect responsibility for an improper use of the actuator not respecting the performances of...

Страница 3: ...CTION 8 4 1 Intended use 8 4 1 1 Use restrictions 8 4 1 2 Standard operating conditions 9 4 1 3 Thermal limit 9 4 2 Personnel requirements Qualifications 9 5 STORAGE 9 6 INSTALLATION 10 6 1 Safety war...

Страница 4: ...4 8 LUBRICATION 20 9 MAINTENANCE 20 9 1 Maintenance of ACL2 ACL2 B 20 25 28 actuators 20 9 2 Maintenance of ACL2 ACL2 B 30 40 actuators 20 9 2 1 Linear drive lubrication 21...

Страница 5: ...he product For all the technical characteristics of the product performance features dimensions refer to the technical catalog Main actuator components 1 Push rod 2 External tube 3 Gearbox housing 4 R...

Страница 6: ...t 1 Product code is an alphanumeric code stating the type of the linear actuator 2 3 Serial number is the identification number of the actuator which identifies the exact design of the product even af...

Страница 7: ...inear actuator the push rod must be in retracted position Lift the actuator from the housing and outer tube supporting the motor during transport DO NOT lift the actuator from the push rod and or the...

Страница 8: ...xial applied load They must be subjected to the loading and speed conditions specified in the catalog Modification of parts of the actuator or replacement of components with different and non original...

Страница 9: ...internal parts overheating 10 10 100 Linear drive Fi Acme screw ACL2 series 30 Ball screw ACL2 B series 100 For the proper operation of acme screw linear actuators ACL2 series do never exceed the perm...

Страница 10: ...OF THE PRODUCT BEFORE TO PROCEED TO THE ELECTRIC CONNECTION MAKE SURE THE SUPPLY VOLTAGE IS TURNED OFF BEFORE TO TURN ON THE MOTOR MAKE SURE THE ELECTRIC CONNECTIONS ARE TIGHTENED AND STABLE CHECK PO...

Страница 11: ...D ACTUATOR stop position Ring 2 activates FC 2 switch and fixes the required EXTENDED ACTUATOR stop position To setup the stop positions simply release the grub screw on the ring move it on the requir...

Страница 12: ...ogue or to the check sheet supplied with the actuator When using more contact reeds for intermediate positions it shall be considered that the same reed switch can give the signal in 2 different posit...

Страница 13: ...ES Contact NC NO Switching output Reed Supply voltage 5 120 V AC DC 1 5 230 V AC DC 2 Voltage drop 0 35 V Continous current 100 mA AC Switching capacity 6 W Protection class II Enclosure rating IP 65...

Страница 14: ...ing IP 55 The rotary encoder ENC 4 must be connected to the electric control circuit as shown in the following WIRING DIAGRAM 6 5 Rotary encoder GI 2X THE ROTARY ENCODER GI 2X IS AVAILABLE ONLY FOR AT...

Страница 15: ...s device is a torque limiter on the worm wheel The torque limiter clutch is preloaded during assembly The preload is fixed and related to the ratio and the performances of each actuator as stated on t...

Страница 16: ...16 6 8 Electric motor wiring PLEASE REFER TO INSTALLATION INSTRUCTIONS OF THE ELECTRIC MOTOR SELECTED FOR THE ACTUATOR...

Страница 17: ...PREVENT DAMAGE TO PERSONS OR PROPERTY Check that all plant fixing elements are well machined and cleaned and that they fit the dimensions of the actuators fixing elements they have to be fixed to If t...

Страница 18: ...E ACTUATOR 6 10Installation of rod end fitting elements To install a mounting element on the rod end threaded bore BA use a wrench flat on the rod end to counterhold the locking torque In case of actu...

Страница 19: ...e actuator then run the actuator GRADUALLY from the control unit in order to reach the plant to its more distant extreme position Check continuously the current actuator length during the motion Repea...

Страница 20: ...OULD BE USED PLEASE CONTACT SERVOMECH BEFORE PROCEED IN CASE OF CUSTOM PRODUCT EXECUTION THE LUBRICANTS COULD BE DIFFERENT FROM THE STANDARD ABOVE TO KNOW THE TYPE OF LUBRICANT PLEASE REFER TO THE PRO...

Страница 21: ...rease nipple type DIN71412 M6 Figure 9 2 Linear drive relubrication of ACL2 ACL2 B 30 40 Apply the grease quantity indicated in Tab 9 1 with several partial quantities Travel over the entire stroke be...

Страница 22: ...SNT 2 rue Marcel Dassault Z I Croix Saint Nicolas 94510 LA QUEUE EN BRIE Tel 01 45 93 05 25 Fax 01 45 94 79 95 Email contact snt tm fr www snt tm fr...

Отзывы: