SMS SenTRI SEN-710 Скачать руководство пользователя страница 1

These instructions are for the SenTRI Sensor product range. A
SenTRI Sensor product integrates smoke and heat detection
with electronic sounder and LED flasher (Strobe) in one
assembly.

Product range

All LPCB approved Sensor STATES are
listed in the

Description and

commissioning

information

These products are not visual alarm devices and do not

meet EN 54-23.

Part number

Description

Symbol

SEN-720

Heat Sensor

H

SEN-780

Heat Sensor plus
Sounder

HS

SEN-780-ST

Heat Sensor plus
Sounder & Strobe

HSSt

SEN-715 #

Optical Sensor

O

SEN-710

Optical & Heat Sensor

OH

SEN-770

Optical & Heat Sensor
plus Sounder

OHS

SEN-770-ST

Optical & Heat Sensor
plus Sounder & Strobe

OHSSt

# This 'Optical' Sensor is also used in the Duct sensor.

Associated products

S4-700
(previously SEN-700)

Base

SEN-FLUSH

Semi-Flush fixing kit

805589

Sensor dust cover
(pack of 50)

805580

Removal tool kit

SEN-COVER-REMOVER Dust cover remover tool

(spare adaptor)

805576

Label plate (pack of 50)

General specification

Operating voltage

35V - 41V

Weight

110g

with base - 170g

SEN-720 only: 88g
(with base - 148g)

Dimensions in mm

117 diameter by
49.6 height

With base the height
increases to 63.8

IP rating

IP30
IP20 when mounted on
a metal back box

Enclosure

ABS

Colour

RAL 9010

Approval

LPCB approved

Storage temperature

-20

°

C to +70

°

C

Ambient operating
temperature

-10

°

C to +50

°

C

Relative humidity

95% non condensing
(+5°C to +45°C)

Heat (H)

Standard

EN54 : Part 5 :2002

Optical (O)

Standard

EN54 : Part 7 : 2002

Sounder (S)

Standard

EN54 : Part 3 : 2002

Multi sensor

Standard

CEA 4021 : 2003-07

EN54-18 : 2005 - Input/ output devices

EN54-17 : 2005
Short-circuit
isolator
(section 4.8)
data:

V

max

42V

I

C max

0.4A

V

nom

40V

I

S max

1A

V

min

24V

I

L max

20

m

A

V

SO max

16V

Z

C max

0.16

W

V

SO min

8V

Information on minimum sound output levels to include polar
dispersion is covered in a technical note TECH7018.033,
available on request from manufacturer.

4188-897 issue 3_12/13_SenTRI Sensor Data_PART-1

1

Data and installation

Sensor, Sounder & Strobe

range

Содержание SenTRI SEN-710

Страница 1: ...t cover remover tool spare adaptor 805576 Label plate pack of 50 General specification Operating voltage 35V 41V Weight 110g with base 170g SEN 720 only 88g with base 148g Dimensions in mm 117 diamete...

Страница 2: ...a monitored input or unmonitored output The factory setting of the programmable input output is an unmonitored output to drive an external repeat LED without a series resistor There is a maximum cabl...

Страница 3: ...lines on the base and SenTRI device will align To fit the dust cover using tool Place the dust cover onto the tool inside the cradle Offer the cover to the SenTRI device locate and push to fit it ont...

Страница 4: ...a 140mm diameter hole in the ceiling tile If required use a Bi Metal Holesaw 140mm or 146mm from www shop4tools co uk Insert the flush shroud assembly into the hole in the ceiling tile Hold the flush...

Страница 5: ...to flash periodically as an in operation confirmation this indication is given system wide at all Sensor Sounder Strobe devices Dust Cover A dust cover is supplied with each Sensor Sounder Strobe dev...

Страница 6: ...e slots The standard outputs are synchronised with the S3 devices installed in the same system A piezo disk within a Sensor Sounder Strobe device assembly outputs the sound via a horn which is constru...

Страница 7: ...Board MCB is always Card 0 There can be up to 2 loop cards installed in a Senator Advance Panel and SENTRI2 Panel The SENTRI 4 Panel have up to 4 loops cards 1 to 4 a Press the MENU ON OFF button b Pr...

Страница 8: ...3 Class A2 heat Area where there is moderate temperature changes plus dust smoke or steam present b STATE 7 Class A2S heat Area where fixed temperature operation is required but is totally unaffected...

Страница 9: ...application in area with low dust smoke or steam present for fixed temperature operation that is totally unaffected by transient temperature variation e STATE 5 Medium sensitivity optical Class B hea...

Страница 10: ...alogue Channel 3 is not applicable Analogue Channel 4 is not applicable Analogue Channel 5 reports sounder flasher bell tone faults to the control panel Analogue Channel 6 reports monitored input moni...

Страница 11: ...avoid possible false alarms 3 The sensor is faulty A fault condition indication is given at the control panel A message reading Sensor Out of Specification is displayed A sensor having code 3 is auto...

Страница 12: ...averages are close to acceptable limits On commissioning the sensor should be replaced A sensor with code 2 is worse than code 1 On maintenance sensors with code 2 should be replaced 0 0 0 0 0 0 1 0 0...

Страница 13: ...imit Out of limits Clean replace 6th Heat channel drift or out of range OK Out of limits Clean replace 7th Optical channel noisy High frequency OK Single HF noise event detected Multiple HF noise seen...

Страница 14: ...nless there is a threshold Checking the time averages The following procedure assumes there is no password access required a Press the Menu On Off button b Select Info and momentarily press etc to sel...

Страница 15: ...h freeblocks ON This is not allowed Switch OFF the freeblocks and reallocate Memory corrupt Device EEPROM checksum failure Replace device Program memory corrupted Card Checksum failure on EPROM at mid...

Страница 16: ...urbo modes When the panel commands a low or high tone output at Sensor Sounder Strobe devices if configured during commissioning the Sensor Sounder Strobe device will output turbo and or non turbo ton...

Страница 17: ...ring password PIN this need only be done if an Engineering password is set up Press etc and select Test and select Zone and toggle select Reset No Reset whatever it reads that is what is selected Now...

Страница 18: ...es should be disposed of via a suitable recycling centre and in accordance with national or local legislation High and Low tone selection or Tone followed by message selection for signals 0 1 2 and 3...

Отзывы: