BACnet Router Start-up Guide
Page 19 of 51
7.2.5 BACnet MS/TP, BACnet Ethernet and BACnet Explorer
•
Max Info Frames
– the number of transactions the
Router may initiate while it has the MS/TP token.
Default is 50.
•
Max Master
– the highest MAC address to scan for
other MS/TP master devices. The default of 127 is
guaranteed to discover all other MS/TP master
devices on the network.
•
MAC Address
– legal values are 0 to 127, must be
unique on the physical network.
•
Baud Rate
– the serial baud rate used on the
network.
•
Token Usage Timeout
(ms)
– the number of
milliseconds the router will wait before deciding that
another master has dropped the MS/TP token. This
value must be between 20ms and 100ms. Choose a
larger value to improve reliability when working with
slow MS/TP devices that may not be able to meet
strict timing specifications.