Model 3600-I IR3 Flame Detector
Page 53 of 66
APPENDIX C. RS-485 COMMUNICATION NETWORK
Appendix C.1. RS-485 Overview
By using the RS-485 network capability of the UV/IR detector and additional software, it is possible to
connect up to 32 detectors in an addressable system with four (4) wires only (2 for power and 2 for
communication). Using repeaters, the number of detectors can be much larger (32 detectors for each
repeater) up to 247 on the same four (4) wires. When using the RS-485 network, it is possible to read
each detector status (FAULT, WARNING, and ALARM) and to initiate a BIT to each detector individually.
For more details, contact Sierra Monitor.
Figure 44: RS-485 Networking