background image

 

Communication Format

 

3-4 

 

INR-244-831 

3.5 

Explanation of Code 

 

  STX 

The code necessary for the receiver to detect the beginning of a 
message. It is put at the beginning of sent characters. 

  Address 

The address to which (this product) the master communicates. The 
address in a response message from this product shows where the 
message is sent.   

  Content 

One of two symbols, R or W. 

R: Read data from the product 

W: Write or store data to the product 

  Identification 

The classification symbol (identification code) of read or written data with 
3 digit alphabetical ASCII codes. Refer to page 3-9 

“3.9 Identification 

Code List

  Numeric data 

Read or written data with 5 digits regardless of its type.   
Minus data: 

“- (symbol for minus)“ is displayed at the 1

st

 digit   

Position of decimal point: Not included in 5 digit data. 
Ex) The 5 digit numeric data means 
 

Ex. 

Meaning of numerical data 

Target temp., measured 
temp., and offset value 

00010: 1.0°C 

Control mode 

00000: Temperature control enable(Run) 
00002: Temperature control diseble(Rdy) 

  ETX 

The code necessary for the receiver to know the message is complete. It 
is put at the end of sent characters (except for BCC). 

  BCC 

Exclusive OR (EX-OR) of all characters from STX to ETX are taken in. 
If 

BCC check is set to “no function” in the comunication setting mode of 

the product, this code is not included in 

the “response message”. 

  ACK 

The affirmation code included in the 

“response message” of the 

product; it is sent when the received 

“request message” contains no 

errors. 

  NAK 

Содержание Thermo-con INR-244-831

Страница 1: ...umber INR 244 831 Serial Communication Manual HEC OM Y010 Keep available whenever necessary This manual is copyrighted and all rights are reserved by SMC Corporation and may not in whole or in part be...

Страница 2: ......

Страница 3: ...INR 244 831 i History Version Preface Contents Chap 1 Chap 2 Chap 3 Chap 4 1 0 Feb 19 21 Feb 19 21 Feb 19 21 Feb 19 21 Feb 19 21 Feb 19 21 Record of Changes Version Contents Date 1 0 First edition Fe...

Страница 4: ...nd safety instructions well Instructions in the categories Danger Warning and Caution are important for safety and must be duly followed Please contact the following for any question and unclear point...

Страница 5: ...OF MESSAGE 3 1 3 2 CONTENT OF COMMUNICATION 3 1 3 3 COMPOSITION OF REQUIRED MESSAGE FROM MASTER TO THE PRODUCT 3 2 3 4 COMPOSITION OF RESPONSE MESSAGE FROM THE PRODUCT TO MASTER 3 3 3 5 EXPLANATION O...

Страница 6: ......

Страница 7: ...tion connector and drop it to FG flame ground Connection drawing for communication is shown in the Figures 1 1 Length of communication cable for RS 485 shall be limited to around 500 m in total If com...

Страница 8: ......

Страница 9: ...or 2 bit Disable Enable 1 to 99 Note Values underlined indicate default values It is set to these values when delivered 2 1 Communication Procedure This product receives a request message from the ma...

Страница 10: ......

Страница 11: ...target temperature 3 Setting and reading of offset value 4 Storage of set value 5 Setting and reading of control mode Tips All set values input by communication function are not stored If they need to...

Страница 12: ...Composition of request message to read Start code Request to read Identification code End code BCC data Address Composition of request message to write W Start code Request to write Identification co...

Страница 13: ...1 to 10 Response message to request message to read Start code Affirmation code Identification code Numerical data End code BCC data Address Response message to request message to write and store Sta...

Страница 14: ...data with 5 digits regardless of its type Minus data symbol for minus is displayed at the 1 st digit Position of decimal point Not included in 5 digit data Ex The 5 digit numeric data means Ex Meaning...

Страница 15: ...then the error that has been assigned the largest number is included and sent Table 3 1 Content and classification of errors Error no Content of the error in a request message 0 Memory error or contr...

Страница 16: ...check the message and resend the necessary request message Address designation error When this error occurs the product does not respond to a request message which specifies an address other than the...

Страница 17: ...est message to read from master Code Symbol Data ASCII code Start code STX 02H Address 01 30H 31H Required content R read 52H Identifier PV1 50H 56H 31H Numeric data 00250 30H 30H 32H 35H 30H End code...

Страница 18: ...reading the data separately Request message to write from master Code Symbol Data ASCII code Start code STX 02H Address 10 31H 30H Required content W write 57H Identifier SV1 53H 56H 31H Numeric data...

Страница 19: ...0 SV1 Set value SV Read Write 00100 00600 PVS Offset setting Read Write 0099 00099 STR Data storage Write _MD note Control mode Read Write 00000 Temperature control enable Run 00002 Temperature contro...

Страница 20: ......

Страница 21: ...ram is made properly according to this operation manual Control code command code BCC check etc The communication method is incorrect Use the communication method suitable for the specification of the...

Страница 22: ...JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL https www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer 2021 SMC Corpor...

Отзывы: