Change of Set Value [3 step setting mode]
3 step setting mode
In the 3 step setting mode, the set value selected in the sub display and the hysteresis can be changed in just
3 steps.
Use this mode if the product is to be used straight away, after changing only the set values.
The current flow value is displayed on the main display
■
Default setting
When the flow exceeds the set value [P_1], the switch will be turned ON.
When the flow falls below the set value by the amount of hysteresis [H_1] or more, the switch will turn OFF.
If the operation shown below is acceptable, then keep these settings.
●
PF3A703H
Item
Default Settings
[P_1] Set value of OUT
1500 L/min
[H_1] Hysteresis of OUT
150 L/min
●
PF3A706H
Item
Default Settings
[P_1] Set value of OUT
3000 L/min
[H_1] Hysteresis of OUT
300 L/min
●
PF3A712H
Item
Default Settings
[P_1] Set value of OUT
6000 L/min
[H_1] Hysteresis of OUT
600 L/min
: For hysteresis, please refer to [F 1] Setting of OUT1 (page
).