-77-
No.PF
※※
-OMZ0002
■
Process data
Process data is the data which is exchanged periodically between the master and device.
This product process data consists of switch output status, error diagnostics, flow measurement value and
temperature measurement value.
(Refer to the table below.)
Bit offset
Item
Notes
0
OUT1 output
0: OFF 1: ON
1
OUT2 output
0: OFF 1: ON
8
Flow diagnosis
0: Within range 1: Out of range (HHH/LLL).
9
Fixed output
0: Normal output 1: Fixed output (for checking output)
15
Error diagnosis
0: Error is not generated 1: Error is generated
16 to 31
Flow measurement value
With sign: 16 bit
Bit offset
31
30
29 28 27 26 25
24
23 22 21 20 19 18
17
16
Item
Flow measurement value (PD)
Bit offset
15
14
13 12 11 10
9
8
7
6
5
4
3
2
1
0
Item
Error
Diagnosis
Fixed
output
Reservation
Flow
Diagnosis
Reservation
OUT2
OUT1
Switch output
•The process data of this product is Big-Endian type.
When the transmission method of the upper communication is Little-Endian, the byte order will be
changed.
Refer to the table below for the Endian type of the major upper communication.
Endian type
Upper communication protocol
Big-Endian type
Such as PROFIBUS and PROFINET
Little-Endian type
Such as EtherNET/IP, EtherCAT and CC-Link IE Field.
Содержание PF2MC7 Series
Страница 1: ...No PF OMZ0002 PRODUCT NAME Digital Flow Switch compatible MODEL Series Product Number PF2MC7 ...
Страница 56: ... 55 No PF OMZ0002 Bottom value display Peak value display ...
Страница 98: ... 97 No PF OMZ0002 Pressure loss PF2MC7501 500 L min PF2MC7102 1000 L min PF2MC7202 2000 L min ...
Страница 101: ... 100 No PF OMZ0002 Lead wire with M8 connector ZS 40 A M12 M8 conversion lead wire ZS 40 M12M8 A ...