Flow Monitor

Operation Manual

PF2A3

/PF2W3

/PF2D3

Installation

•Never mount the product in a location that will be used as a foothold.

Thank you for purchasing an SMC PF2A3

/PF2W3

/PF2D3

Series Flow

Monitor.
Please read this manual carefully before operating the product and make sure you
understand its capabilities and limitations.
Please keep this manual handy for future reference.

To obtain more detailed information about operating this product, please
refer to the SMC website (URL http://www.smcworld.com) or contact SMC
directly.

Safety Instructions

These safety instructions are intended to prevent hazardous situations and/or
equipment damage.
These instructions indicate the level of potential hazard with the labels of
"Caution", "Warning" or "Danger". They are all important notes for safety and must
be followed in addition to International standards (ISO/IEC) and other safety
regulations.

CAUTION indicates a hazard with a low level of risk
which, if not avoided, could result in minor or
moderate injury.

Operator

This operation manual is intended for those who have knowledge of machinery
using pneumatic equipment, and have sufficient knowledge of assembly,
operation and maintenance of such equipment. Only those persons are
allowed to perform assembly, operation and maintenance.
Read and understand this operation manual carefully before assembling,
operating or providing maintenance to the product.

Caution:

Warning:

Danger:

WARNING indicates a hazard with a medium level of
risk which, if not avoided, could result in death or
serious injury.

DANGER indicates a hazard with a high level of risk
which, if not avoided, will result in death or serious
injury.

Safety Instructions

Do not disassemble, modify (including changing the printed circuit board) or repair.

An injury or failure can result.

Do not operate in an atmosphere containing flammable, explosive or corrosive gas.

Fire or an explosion can result.
This product is not designed to be explosion proof.

Do not touch the piping or its connected parts when the fluid is at high temperature.

It may lead to burnt.
Ensure the piping cools sufficiently before touching.

Do not use the product in a place where static electricity is a problem.

Otherwise it can cause failure or malfunction of the system.

If using the product in an interlocking circuit:
•Provide a double interlocking system, for example a mechanical system
•Check the product regularly for proper operation

Otherwise malfunction can result, causing an accident.

The following instructions must be followed during maintenance:
•Turn off the power supply
•Ensure the flow is shut off before performing maintenance

Otherwise an injury can result.

After maintenance is complete, perform appropriate functional inspections and leak tests.

Stop operation if the equipment does not function properly or there is a leakage of fluid.
When leakage occurs from parts other than the piping, the product might be faulty.
Disconnect the power supply and stop the fluid supply.
Do not apply fluid under leaking conditions.
Safety cannot be assured in the case of unexpected malfunction.

Do not touch the terminals and connectors while the power is on.

Otherwise electric shock, malfunction or damage to the product can result.

Do not operate the product outside of the specifications.

Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.

Warning

Caution

Maintenance

How to reset the product after a power cut or forcible de-energizing

The setting of the product will be retained as it was before a power cut or 
de-energizing.
The output condition is also basically recovered to that before a power cut or
de-energizing, but may change depending on the operating environment.
Therefore, check the safety of the whole installation before operating the product.

Summary of Product parts

Mounting and Installation

Indicator LED (OUT1)

button (UP)

LED display

Panel mount adapter

button (SET)

Indicator LED (OUT2)

button (DOWN)

Indicator LED

Item

Installing
Removing the panel mount adapter

•Remove the panel mount adapter from the product if it has been delivered

assembled.

•Remove the mounting bracket using a flat blade screwdriver.

Hook

•Lever the hook to the outside to remove the adapter (See below).
•If the panel mount adapter is pulled with the hook engaged, the product or

the panel mount adapter will be damaged.

Front

Description

Terminal block

Terminals to connect the power, output and sensor wires.
For details, refer to Wiring.

Terminal block

Item

Back

Description

LED display

Displays the flow value, setting mode, and error indication.

Indicator LED

Indicates the reference condition selected. LED is ON (Red) when normal condition is
selected. (Only the PF2A3

)

Panel mount adapter

Adapter to mount the product to the panel.

Indicator LED (OUT1)

Indicates the output status of OUT1. LED is ON (Green) when OUT1 is ON.
The LED flashes when an over current error occurs.
When the accumulated pulse output mode is selected, the indicator LED will turn OFF.

Indicator LED (OUT2)

Indicates the output status of OUT2. LED is ON (Red) when OUT2 is ON.
The LED flashes when an over current error occurs.
When the accumulated pulse output mode is selected, the indicator LED will turn OFF.

button (UP)

Selects the mode or increases the ON/OFF Set value.

button (SET)

Press this button to change to another mode and to set a value.

button (DOWN)

Selects the mode or decreases the ON/OFF Set value.

+

PF2A30    series

PF2A550

PF2A510

PF2W511

PF2D520

PF2D540

PF2D504

Connected sensor

Di

sp

la

in

st

an

ta

ne

ou

flo

 D

isp

lay

    

 ac

cu

mu

lat

ed

 flo

w

2 sec.

2 sec. or longer

Display mode

Display

accumulated flow

Display

instantaneous flow

3 sec. or longer

3 sec. or longer

Input the Set value of

instantaneous output

(Auto-preset)

Input the Set value of

accumulated output

Input the Set value of

instantaneous output

Input of the Set point 1

(OUT1)

Input of the Set point 2

(OUT1)

Input of the Set point 3

(OUT2)

Measurement of the 

Set value (OUT1)

Input of the Set value for the

lower 3 digits (OUT1)

Input of the Set value for the

upper 3 digits (OUT1)

Input of the Set value for the

lower 3 digits (OUT2)

Input of the Set value for the

upper 3 digits (OUT2)

Function selection mode

Measurement of the

Set value (OUT2)

Flow

Set value is calculated and set.

Flow

Set value is calculated and set.

Display instantaneous flow 

 Display accumulated flow

Display accumulated flow

Accumulated value is reset

Display instantaneous flow

Display upper 3 digits

Accumulated

output mode

Accumulated pulse

output mode

Instantaneous

output mode

Output mode (OUT1)

Accumulated

output mode

Accumulated pulse

output mode

Instantaneous

output mode

Output mode (OUT2)

Unit selection function 

1

L/min,L

Non-Reverse

output

Reverse

output

Switch operation (OUT2)

Non-Reverse

output

Reverse

output

Normal

condition

Standard

condition

標準状態

Reference condition  

2

CFM x 10

-2

,

CFM x 10

-1

, ft

3

 x 10

-1

gal(US)/min, gal(US)

Indicator LED

Switch operation (OUT1)

Measurement mode (Instantaneous flow)

: Start the setting here to supply power under the default settings.

Measurement mode (Accumulated flow)

Accumulation stop

Accumulation starts

Press

and

PF2A511

PF2A521

PF2A551

PF2A31    series

PF2W520

PF2W540

PF2W504

PF2W30    series

PF2W33    series

PF2D30    series

2 sec.

4

Set value

or      

3

4

Set value

or      

3

4

4

4

Set value

Set value

Set value

or      

3

4

Set value

or      

3

4

Set value

or      

3

4

Set value

or      

3

4

Set value

or      

3

4

Set value

or      

3

Unlock

Lock

Unlock

Lock

Key-lock function

Initialize mode

Key-lock function

1: Operate only the product with unit selction function (Model indication: without M).

2: Operate only the PF2A3      series.

3: Depend on the setting of switch operation in initialize mode.

4: Displayed in turn.

Input of the Set point 4

(OUT2)

: Accumulation starts and “-” flashes.

List of outputs

Find the diagram of the output required in the table below. Perform settings
following the Set value column on the right. Characters in ( ) are for OUT2.

Setting flow chart

Flow has exceeded the upper
limit of the display flow range.

Reduce the flow.

Error type

Troubleshooting method

Error indication

The switch output load current
is more than 80 mA (OUT1).

Turn the power off and remove the
cause of the over current.
Then turn the power on again.

The switch output load current
is more than 80 mA (OUT2).

The display flow range of
accumulated flow has been
exceeded.

To reset, press 

and 

buttons

simultaneously for 2 seconds or longer.
Then set all data again.

The set data has been changed
unexpectedly.

To reset the accumulated flow value,
press

and 

buttons simultaneously

for 2 seconds or longer.

Key-lock function

This function is used to prevent errors occurring due to unintentional changes of
the set values.

Excessive
instantaneous flow

Error name

OUT1
over current error

OUT2
over current error

Excessive
accumulated flow

System error

Initialize mode

Default settings

The default settings are as follows.
If this condition is acceptable, then keep these settings.

[F_1] Input the Set value of

instantaneous output

[n_1] Input of the Set point 1 (OUT1)

Function selection mode

Item

Default settings

The default settings are as follows.
If this condition is acceptable, then keep these settings.

[n_2] Input of the Set point 2 (OUT1)

[n_3] Input of the Set point 3 (OUT2)

[n_4] Input of the Set point 4 (OUT2)

[F_2] Input the Set value of

instantaneous output
(Auto-preset)

-

[F_3] Input the Set value of

accumulated output

[1nL] Input of the Set value for the lower 3 digits (OUT1)

[1nH] Input of the Set value for the upper 3 digits (OUT1)

: When Non-Reverse output is selected as the switching operation, n becomes P.

In measurement mode, press the 

button, to display [F_ ].

This [F_ ] indicates the mode for changing each functional setting.

: When OUT1 or OUT2 is assigned to be instantaneous output mode during initialize mode, [F_1] and [F_2] are

displayed.
When OUT1 or OUT2 is assigned to be accumulated output mode, [F_3] is displayed.

50% of max. rated flow

Default setting

50% of max. rated flow

50% of max. rated flow

50% of max. rated flow

-

[    0]

[    0]

[2nL] Input of the Set value for the lower 3 digits (OUT2)

[2nH] Input of the Set value for the upper 3 digits (OUT2)

[    0]

[    0]

Items below can be set.
•Connected sensor                •Display mode                 •Unit selection function

•Output mode (OUT1)

•Output mode (OUT2)     •Switch operation (OUT1)

•Switch operation (OUT2)

•Reference condition

Troubleshooting

Mounting with the panel mount adapter

•Install the product as shown below.
•Insert panel mount adapter B into section A of panel mount adapter A.

Push panel mount adapter B from behind until the display is fixed onto the panel.
The pin of panel mount adapter B engages the notched part of panel adapter
section A to fix the display.

Panel mount adapter A

A

Panel

Panel mount adapter B

Press

Insert

Mounting bracket

Wiring

•Connections should only be made with the power supply turned off.
•Use separate routes for the product wiring and any power or high voltage

wiring. Otherwise, malfunction may result due to noise.

•Ensure that the FG terminal is connected to ground when using a commercially

available switch-mode power supply. When a switch-mode power supply is
connected to the product, switching noise will be superimposed and the
product specification can no longer be met. This can be prevented by inserting
a noise filter, such as a line noise filter and ferrite core, between the switch-
mode power supply and the product, or by using a series power supply instead
of a switch-mode power supply.

Connecting the wiring

•Use suitable crimp terminals for connection to the terminal block.
•Attention should be paid to the terminals to avoid short circuits.

1 2 3 4

5 6 7 8

Terminal block number

3

5

2

1

4

DC(-) (for sensor)

Sensor input

N.C.

DC(-) (supply voltage)

DC(+) (for sensor)

6

8

7

DC(+) (supply voltage)

OUT1

OUT2

Power is supplied

Outline of setting

The output will not operate for 3 seconds after supplying power.

The identification code of the product is displayed.

Measurement mode

The mode in which the flow is detected and displayed,

and the switch function is operating.

This is the basic operating mode;

and other modes should be selected for setting

changes and other function settings.

Initialize mode

Function

selection mode

Key-lock function

button

press for
2 sec.

button

press.

button

press for
3 sec.

In

s

ta

n

ta

n

e

o

u

s

 f

lo

w

Switch output diagram

Output mode

Switch operation

Set value

Instantaneous

output mode

(

)

Non-Reverse

output

(

)

Set point 2     Set point 1

(

)

Hysteresis mode

2

Set point 1     Set point 2

(

)

Window comparator mode

Set point 1

Set point 2

(

)

Window comparator mode

Reverse output

(

)

OFF

ON

Hysteresis

P_2

(P_4)

P_1

(P_3)

Instantaneous

flow

OFF

ON

Hysteresis 

1

Hysteresis 

1

P_1

(P_3)

P_2

(P_4)

Instantaneous

flow

OFF

ON

Hysteresis

n_2

(n_4)

n_1

(n_3)

Instantaneous

flow

OFF

ON

Hysteresis 

1

Hysteresis 

1

n_1

(n_3)

n_2

(n_4)

Instantaneous

flow

Set point 2     Set point 1

(

)

Hysteresis mode

2

A

c

c

u

m

u

la

te

d

 f

lo

w

Accumulated
output mode

(

)

Non-Reverse

output

(

)

Upper 3 digits

Lower 3 digits

+

(

+

)

Upper 3 digits

Lower 3 digits

+

(

+

)

Reverse output

(

)

OFF

ON

Time

Time

Accumlated flow

1PH+1PL

(2PH+2PL)

OFF

ON

Time

Time

Accumlated flow

1nH+1nL

(2nH+2nL)

A

c

c

u

m

u

la

te

d

 p

u

ls

e

Accumulated

pulse output

mode

(

)

No Set value input

No Set value input

Reverse output

(

)

OFF

ON

Time

50 ms

OFF

ON

Time

50 ms

Error display

Accumulated 

flow displayed

(flashing)

: If the error cannot be reset after the above measures are taken, then please contact SMC.

Specification / Outline with Dimensions

Refer to the product catalogue or SMC website (URL http://www.smcworld.com) for
more information about product specifications and outline dimensions in detail.

Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2011 SMC Corporation All Rights Reserved

Akihabara UDX 15F, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, JAPAN
Phone: +81 3-5207-8249   Fax: +81 3-5298-5362

URL http://www.smcworld.com

Non-Reverse

output

(

)

Refer to the SMC website (URL http://www.smcworld.com) for more information
about troubleshooting.

1: In window comparator mode, the hysteresis is fixed at 3 digits. When setting, allow 7 digits or more between 

Set point 1 and Set point 2 (Set point 3 and Set point 4).

2: When Set point 1 = Set point 2 (Set point 3 = Set point 4), chattering may occur.

Selection of display mode

[d_1] Display instantaneous flow

Item

Default settings

Unit selection function

[U_1] L/min

Selection of output mode (OUT1)

[o10] Instantaneous output mode

Selection of output mode (OUT2)

[o20] Instantaneous output mode

Selection of switch operation (OUT1)

[1_n] Reverse output

Selection of switch operation (OUT2)

[2_n] Reverse output

Selection of reference condition

[Anr] Standard condition

Selection of the connected sensor

[10L] 1 to 10 L/min type (PF2A510)

[04L] 0.5 to 4 L/min type (PF2W504)

[04d] 0.4 to 4 L/min type (PF2D504)

Common

Model

Common

Common

Common

Common

Common

PF2A3

series only 

PF2A30

series

PF2W30

series

[11L] 10 to 100 L/min type (PF2A511)

[11L] 10 to 100 L/min type (PF2W511)

PF2A31

series

PF2W33

series

PF2D3

series

Refer to the product catalogue or SMC website (URL http://www.smcworld.com)
for more detailed information about panel cut-out dimensions.

: Operate only the product with unit selection function.