85

 - 

 

 

7.4 Positioning Mode (Point table method) 

Positioning  operation  can  be  executed  by  setting  the  target  position,  rotation  speed,  acceleration  time  constant, 
deceleration time constant to the point table data. (The maximum points that can be set in point table is 7.) 

 

See 

LEC

SA Operation Manual”,section 13.3 for details regarding the positioning mode (point table). 

 

7.4.1 Operation Instruction of Point Table system 

Select the point table No. represented by the values of DI0, DI1 and DI2. Start the operation by selecting ST1 or 
ST2. 

 

Device 

Symbol 

Connector 

pin No. 

Functions/Applications 

I/O 

division 

Positioning 

mode 

CP 

CL 

Point table No. 

/Program No. 

selection 1 

DI0 

CN1-5 

<In point table method> 

The point table No. and the home position return 

mode are selected by DI0 to DI2. 

<In program method> 

The program No. is selected by DI0 to DI2. 

 

DI-1 

 

 

 

 

 

 

  (Note) 

Device 

Selection description 

 

 

 

 

Point table No. 

/Program No. 

selection 2 

DI1 

CN1-23 

 

DI2  DI1  DI0 

Point table method 

 

DI-1 

 

 

 

 

 

Home position return mode 

 

 

 

 

 

 

 

Point table No. 1 

 

 

 

 

 

 

 

Point table No. 2 

 

 

 

 

 

 

 

Point table No. 3 

 

 

 

 

 

 

 

Point table No. 4 

 

 

 

 

Point table No. 

/Program No. 

selection 3 

DI2 

 

 

Point table No. 5 

 

DI-1 

 

 

 

 

Point table No. 6 

 

 

 

 

 

 

Point table No. 7 

 

 

 

 

 

Note. 0: off 

  1: on 

 

 

 

 

Program   

input 1 

PI1 

 

Turn PI1 on to resume the step stopped by the 

SINK (1) command in the program. 

DI-1 

 

 

 

If the parameter " PE01

Command mode selection " setting is "0000

Absolute value command system " .   

Point table No. 

Target position 

[×10

STM

μm] 

Rotation speed 

[r/min] 

Acceleration 

time constant 

[ms] 

Deceleration 

time constant 

[ms] 

Dwell 

[ms] 

Auxiliary 

function 

5.00 

3000 

100 

150 

100 

-6.00 

2000 

100 

100 

3.00 

3000 

50 

50 

0 (Note)   

Note. Always set "0" or "2" to the auxiliary function in the last point table among the consecutive point tables. 

0: When point table is used in absolute value command system 

2: When point table is used in incremental value command system 

 

Содержание LECSA Series

Страница 1: ...PRODUCT NAME AC Servo Motor Driver Pulse input type Positioning type MODEL Series Product Number LECSA Series Simplified Edition LEC OM05611 Doc No JXC OMT0052 A...

Страница 2: ...No No No No JXC OMT0052 LEC OM05610 JXC OMT0052 A LEC OM05611...

Страница 3: ...software MR Configurator2TM 19 5 1 1 Installation Method 19 5 2 Basic driver set up for Initial Test Drive 19 5 2 1 Start up the Setup software MR Configurator2TM 20 5 2 2 System Settings 21 5 2 3 Mod...

Страница 4: ...Saving Loading Project 65 5 9 1 Saving Project 65 5 9 2 To Load saved Project 66 5 10 Saving Loading Point table 67 5 10 1 Saving Point table 67 5 10 2 To Load saved Point table 68 5 11 Acquisition of...

Страница 5: ...3 8 Troubleshooting 91 8 1 Alarms and Warning List 91 8 2 Alarm Display 93...

Страница 6: ...Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly operation and maintenance of machines...

Страница 7: ...tance or replacement parts Please consult your nearest sales branch For any failure or damage reported within the warranty period which is clearly our responsibility a replacement product or necessary...

Страница 8: ...ning Positioning mode Point table Set the positioning data rotation speed Acceleration Deceleration time constant of the drivers point table and execute ON OFF control of the positioning operation usi...

Страница 9: ...e position return Method Position Control Mode Configuration See 7 1 Position Control Mode Pulse input Positioning mode Configuration See 7 4 Positioning mode Point table method See 7 5 Positioning Mo...

Страница 10: ...orced stop Note 5 Servo on RA OFF Trouble MC ON MC SK Note 5 Forced stop Note 6 Circuit protector Note 4 Note 2 Note 3 Note 3 24VDC Note 7 Note 1 Built in regenerative resistor 1 Power supply input te...

Страница 11: ...Note 10 11 Note 9 Servo on Reset 10m max Note 1 USB cable option MR Configurator CN3 Personal computer Note 14 Note 15 Servo amplifier 10m max 2m max Note 8 Note 7 Programmable logic controller FX3U M...

Страница 12: ...opped suddenly and servo lock is enabled LSN Reverse rotation stroke end Turn this signal on before operation When this signal turns off the product is stopped suddenly and servo lock is enabled TL1 I...

Страница 13: ...In position This signal turns on when the droop pulse is within the setting range SA Speed reached When the servo motor rotation speed reaches the set speed this signal turns on VLC Limiting speed Thi...

Страница 14: ...er Control common Encoder Z phase pulse open collector Encoder Z phase pulse differential line driver 19 20 LZR CN1 1 13 DICOM DOCOM 10m max USB cable option CN3 MR Configurator Personal computer 24VD...

Страница 15: ...ntrol common Encoder Z phase pulse open collector CN1 Ready Encoder Z phase pulse differential line driver 19 LZ LZR Note 6 CN1 1 13 DICOM DOCOM Personal computer USB cable option CN3 10m max Note 7 M...

Страница 16: ...er 19 20 LZR Note 7 CN1 1 13 DICOM DOCOM 10m max CN3 Note 8 MR Configurator Personal computer 24VDC RA1 RA2 RA3 RA4 Note 4 9 Note 9 11 8 4 3 7 Forced stop Servo on Automatic manual selection Forward r...

Страница 17: ...c Servo amplifier Switch Approx 5mA DICOM VCES 1 0V ICEO 100 A 24VDC 10 200mA Approx 5 6k 2 Digital output interface DO 1 A maximum voltage drop of 2 6V may occur in the driver Note 24VDC 10 2 00mA If...

Страница 18: ...Basic settings parameters No PA No Symbol Name Initial value Unit PA01 STY Control mode 000h 2 I O setting parameters No PD These parameters are set when changing the input output signal assignment a...

Страница 19: ...d 4 Applied 200 r min PC32 SC5 Internal speed command 5 Applied 300 r min PC33 SC6 Internal speed command 6 Applied 500 r min PC34 SC7 Internal speed command 7 Applied 800 r min 4 4 Torque control mod...

Страница 20: ...e Initial value Unit PE01 CTY Command mode selection 0000h PE02 FTY Feeding function selection 0000h PE03 ZTY Home position return type 0010h PE04 ZRF Home position return speed 500 r min PE06 ZST Hom...

Страница 21: ...setup software MR Configurator2TM LEC MRC2E must be purchased as an additional item 3 The USB cable LEC MR J3USB must be purchased as an additional item 5 1 1 Installation Method Perform installation...

Страница 22: ...up the Setup software MR Configurator2TM Connect the PC and LECSA using the USB cable Turn on the power of the LECSA Start application MR Configurator2 Once the application starts the screen below wi...

Страница 23: ...to change parameter PC40 to 0 The default value of parameter PC40 is 0 When using LECSA for the first time please use the default parameter for PC40 as 0 Please select servo amplifier connection USB...

Страница 24: ...n Is the PC and LECSA amplifier connected with the USB cable Is the USB driver installed Is the USB driver which is compliant to Windows version installed Is parameter PC40 set to 0 PC40 is a paramete...

Страница 25: ...J3USB must be purchased as an additional item From the Parameter menu select Parameter Setting the parameter setting window will open The explanation of the parameter item is displayed in MR2 Help Whe...

Страница 26: ...o not cycle the power it does not register the data in the driver Note2 Selected Items Write It writes the parameter values of the corresponding frame to the driver Single Axis Write Writes all of the...

Страница 27: ...control mode pulse input Set the parameters of the PA01 to 000 in the Basic tab Setting example of the Control mode PA01 in the case of setting to Positioning Point table Set the parameters of the PA0...

Страница 28: ...Home position return position data m PE08 0 2000 1000 stroke 200 1000 stroke Stopper type home position return stopper time msec PE10 100 200 Stopper type home position return torque limit value PE11...

Страница 29: ...home position return torque limit value PE11 15 30 Regenerative option PA02 000 000 Non 002 LEC MR RB 032 Rotation direction selection PA14 0 1 Counter motors side 0 Counter motors side 1 Counter mot...

Страница 30: ...1000 stroke Stopper type home position return stopper time msec PE10 100 200 Stopper type home position return torque limit value PE11 15 30 Regenerative option PA02 000 000 Non 002 LEC MR RB 032 003...

Страница 31: ...me position return stopper time msec PE10 100 200 Stopper type home position return torque limit value PE11 15 30 Regenerative option PA02 000 000 Non 002 LEC MR RB 032 Rotation direction selection 4...

Страница 32: ...0 100 200 Stopper type home position return torque limit value PE11 15 30 Regenerative option PA02 000 000 Non 002 LEC MR RB 032 003 LEC MR RB 12 Rotation direction selection 4 PA14 0 0 Counter motors...

Страница 33: ...multiplying factor numerator 1 1 to 65535 PA07 CDV Electronic gear denominator Command pulse multiplying factor denominator 1 1 to 65535 1 Complete configuration as shown below Ex Travel amount per 1...

Страница 34: ...parameter in the Basic tab of the List display also changes to 000 To use positioning mode point table navigate to the Basic tab of the Parameter Setting screen Control mode selection Please select P...

Страница 35: ...tion Internal speed Internal torque PA13 PLSS Command input pulse form 000h Refer to the text Select the input form of the pulse train input signal Command pulses may be input in any of three differen...

Страница 36: ...34 Set the PA13 to 201 in the Basic tab Click on the Single Axis Write button Turn the power OFF and ON again Parameter is enabled...

Страница 37: ...parameter perform Verify Click the Verify button on the Parameter Setting window Verfication Setting screen will display Please select the comparison target Amplifier Compare with the parameters set...

Страница 38: ...ter storage method Click the Set To Default button on the Parameter Setting window Please click Yes button Parameter Block screen will display Set the default using an editable parameter as the browsa...

Страница 39: ...isplayed by selecting Jog Mode from the Test Mode menu in the setup software Click OK When using this function all external input signal operation will be diabled If controlling using a PLC or other u...

Страница 40: ...the rotation direction of the actuator does not change if you change the setting of parameter PA14 Rotation direction selection The actuator moves in the direction of Forward CCW button and Reverse CW...

Страница 41: ...Input signal automatic ON selection settings defines which input signals will turn ON automatically when the control circuit power supplyis turned on doing this allows additional I O signal selection...

Страница 42: ...positioning mode point table congifure the operation mode using automatic manual selection MD0 The MD0 off selection will allow Jog operation and it will require an input reserved for MD0 For Automati...

Страница 43: ...ion 13 2 3 for details regarding signals See LECSA Operation Manual section 4 4 2 for details on parameter setting values Pins CN1 23 and CN1 25 can be allocated in current Sink NPN interface interfac...

Страница 44: ...tup Software The Parameter Setting window will be displayed when parameter list is selected from the parameters menu in the setup software Click the I O tab When changing the allocation of signals par...

Страница 45: ...43 5 5 4 Allocation Examples for Position Control Mode Pulse Input 1 Example of Gain switch CDP Settings When changing pin CN1 4 from Servo on SON to Gain switch CDP Changing PD05 from 0202 to 0211 1...

Страница 46: ...ick on the Single Axis Write button Cycle the power off then on for the parametersto be enabled Please allocate pins CN1 4 separately See LECSA Operation Manual section 4 4 2 for details on allocation...

Страница 47: ...he default allocation allocates signals DI0 to CN1 5 and DI1 to CN1 23 Note CN1 23 can only be used if the input is configured as current sink NPN 8 points can be specified however 1 point is reserved...

Страница 48: ...7 Points in current SINK NPN Interface Changing pin CN1 7 from Reverse rotation start ST2 to point table no program no selection 3 DI2 Change PD12 from 0808 to 2E08 Note CN1 23 can only be used if the...

Страница 49: ...tion MD0 to point table no program no selection 3 DI2 Changing pins CN1 7 from Reverse rotation start ST2 to point table no program no selection 2 DI1 Change PD04 from 2003 to 2E03 Change PD12 from 08...

Страница 50: ...nd then on for the parameters to be enabled Complete pin CN1 7 allocation separately See LECSA Operation Manual section 4 4 2 for details on allocation of input signals to pins CN1 3 CN1 8 See LECSA O...

Страница 51: ...8 have been changed It is necessary to confirm these are correctly assigned From the Monitor menu of the Setup Software select I O Monitor The I O Monitor window opens and displays the inputs and outp...

Страница 52: ...indow opens Check Command pulse unit Electronic gear valid and click OK Electronic gear ratio that is set in the PA05 PA06 PA07 is enabled Click OK When using this function external input signal opera...

Страница 53: ...verse CW button Check the command impulse unit electronic gear enabled The electronic gear duty set to PA05 PA06 PA07 will be enabled See LECSA Operation Manual Simplified Edition section 5 3 4 Parame...

Страница 54: ...ate if this is set to 0 If the rotation speed is too low this may cause vibration check the actuator while changing settings Movement speed mm s must be converted into rotation speed r min See below f...

Страница 55: ...d for each actuator The acceleration deceleration time must be converted from the acceleration deceleration speed See below for the conversion formula Calculating Acceleration deceleration conversion...

Страница 56: ...ual Simplified Edition section 5 3 4 the travel distance of the actuator per 1 pulse will be as follows Position control mode pulse input travel distance of the actuator per 1 pulse 10 m 0 01 mm Posit...

Страница 57: ...nt table mode the point table target position speed data acceleration time deceleration time etc must be configured 5 7 1 Point table List Using the Positioning Data menu in the setup software The Poi...

Страница 58: ...nt table in the incremental value command system 2 Automatic operation is performed in accordance with a single point table chosen 3 Operation is performed in accordance with consecutive point tables...

Страница 59: ...00mm set parameter PE02 Feed function selection to 0001 and the Feed length multiplication STM Multiplier value to x10 Set the feed length multiplication STM Multiplier of target position in parameter...

Страница 60: ...ngth multiplication STM Multiplier Feed unit m Target position input range mm 1 999 999 to 999 999 10 9999 99 to 9999 99 100 99999 9 to 99999 9 1000 999999 to 999999 For actuators with a stroke less t...

Страница 61: ...t to a value within the stroke range If electronic gear parameters PA05 PA06 PA07 are set according to LECSA Operation Manual Simplified Edition section 5 3 4 in positioning mode The smallest unit for...

Страница 62: ...elow for the conversion formula Example using a 20 mm Lead Actuator with target travel speed of 500 mm sec The rotation speed must be a value between 0 and the allowable actuator speed The actuator wi...

Страница 63: ...3000 mm s2 133 ms The acceleration time constant deceleration time constant defines the time in ms when the motor rotations of 3000 min are met The acceleration time constant deceleration time constan...

Страница 64: ...ct point table number Press Start The actuator will set the position at which the power was turned on as the home position 0 and move towards the defined point table position Check parameters PA05 PA0...

Страница 65: ...select Save As Please specify location to be saved Please enter any file name Click Save Files Saved prm2 Settings files for parameters PA PB PC PD and PE Note Always upload current parameters from t...

Страница 66: ...saved Parameters From the Parameter Setting window in the setup software select Open Please specify location of the file Please select the file you wish to import parameters prm2 Click Open Parameter...

Страница 67: ...ase enter any file name Click Save Project will be saved in the specified folder If you change the drive path name it will be saved in the drive path name project name folder you have changed Note Alw...

Страница 68: ...om the Project menu in the setup software select Open Please select the drive path name project name that you want to read parameters are stored Please select the file you wish to import project mrc2...

Страница 69: ...67 5 10 Saving Loading Point table 5 10 1 Saving Point table From the Point Table window in the setup software select Save As Please specify location to be saved Please enter any file name Click Save...

Страница 70: ...ad saved Point table From the Point table window in the setup software select Open Please specify location of the file Please select the file you wish to import point table ptb2 Click Open Point table...

Страница 71: ...h graph monitor With the setup software MR Configurator2TM LEC MRC2E monitor graph function the motion waveform during electric actuator operation can be obtained as described below Click Monitor Grap...

Страница 72: ...etting window to set the items to display the waveform trigger conditions and horizontal axis of the graph 3 types analogue waveforms analogue 1 to 3 and 4 types of digital waveforms digital 1 to 4 ca...

Страница 73: ...are displayed Click of Level Condition to set the condition For Motor speed when the operation direction is positive Level should be100 and when the operation direction is negative Level should be 10...

Страница 74: ...00 pulse The displayed number of pulses is units of the encoder pulses 100pulse 7 Droop pulse by 1 pulse The droop pulse on the deviation counter is displayed in units of 1 pulse Note Any area beyond...

Страница 75: ...played in An overload alarm will occur when margin is 0 0 1 19 Excessive error alarm margin The margin until the error reaches the excessive error AL 52 alarm level is displayed in encoder pulses An e...

Страница 76: ...waveforms can be captured and displayed Click the Start button every time measurement fresh capture is required The advantage of this method of capturing the waveform is a waveform will not be updated...

Страница 77: ...er conditions in 5 11 1 2 are satisfied the operation waveforms can be captured When the time set in 5 11 1 1 has passed after the acquisition start the acquisition of the waveforms will complete and...

Страница 78: ...ed and save the data Waveform data file extension gpf2 will be prepared If the waveform condition needs to be checked it can be displayed on the graph window Click the Save Image button Select the fol...

Страница 79: ...exceed 999999999 it returns to zero Press the Clear button to reset the display value to 0 zero Reverse rotation is indicated by a minus sign 999999999 to 999999999 pulse 2 Servo motor speed The serv...

Страница 80: ...isplayed in encoder pulses The value returns to 0 when it exceeds the maximum number of pulses 0 to 262143 pulse 11 Load inertia moment ratio The estimated ratio of the servo motor axis converted iner...

Страница 81: ...turn method using a proximity dog Used when it is minimisation of the proximity dog length is required Data set type An arbitrary position defined as a home position No proximity dog required Stopper...

Страница 82: ...DI0 DI1 and DI2 Program metho Program Select a program that has the home position return ZRT command Stopper type home position return Parameter No PE03 3 Stopper type home position return is selected...

Страница 83: ...ing delays in output signal sequence from the PC or PLC and variations of a signal change due to hardware 2 TLC turns ON when the torque reaches the value set in forward torque limit parameter No PA11...

Страница 84: ...After changing gain Before changing gain Change of each gain CDT 100ms 63 4 Droop pulses pulses 0 Command pulse Droop pulses CDL CDL 95ms 95ms Electromagnetic brake interlock MBR Note 1 ON ON OFF 0 r...

Страница 85: ...position Connect the wirings as follows when operating in forward or reverse rotation with the internal speed command set to the eighth speed Note that the inputs are configured as Current sink NPN Ty...

Страница 86: ...otation in regenerative mode 1 0 CW forward rotation in driving mode reverse rotation in regenerative mode 1 1 Torque is not generated Note 0 off 1 on Generally make connection as shown below Note tha...

Страница 87: ...Note Device Selection description Point table No Program No selection 2 DI1 CN1 23 DI2 DI1 DI0 Point table method DI 1 0 0 0 Home position return mode 0 0 1 Point table No 1 0 1 0 Point table No 2 0...

Страница 88: ...h match CPO Point table No Servo motor speed Forward rotation Reverse rotation 0r min ON OFF Forward rotation start ST1 1 ON OFF Note 2 Travel completion MEND Point table No output PT0 to PT2 3ms or l...

Страница 89: ...ll Stop time Auxiliary functions Driver operation display U UP P D DO OW WN N When the set value is flashing it is not registered When the set value is flashing it is not registered a The set screen c...

Страница 90: ...m 1 Setup software version 1 52E or above is required 2 Setup software should be prepared by the user 3 USB cable LEC MR J3USB is required for software installation See LECSA Operation Manual section...

Страница 91: ...ption SPN Speed Motor speed SPN Setting value 0 to instantaneous permissible speed r min Used to set the command speed of the servo motor for positioning The set value should be equal to or less than...

Страница 92: ...ogram No 5 Point table No Program No selection 3 DI2 1 0 1 Program No 6 DI 1 1 1 0 Program No 7 1 1 1 Program No 8 Note 0 off 1 on Program input 1 PI1 Turn PI1 on to resume the step stopped by the SIN...

Страница 93: ...1 RAM A 13 Clock error A 15 Memory error 2 EEP ROM A 16 Encoder initial communication error1 A 17 Board error A 19 Memory error 3 Flash ROM A 1A Motor combination error A 1C Software combination error...

Страница 94: ...e 2 A 99 Stroke limit warning Stops Note 2 A E0 Excessive regeneration warning Does not stop A E1 Overload warning 1 Does not stop A E6 Servo forced stop warning Stops A E9 Main circuit off warning St...

Страница 95: ...tion history is listed for alarms that occurred in the past Click Diagnosis Alarm Display of the setup software to display Alarm Display window Alarms warnings currently occurring in the driver displa...

Страница 96: ...4 7th printing No LEC OM05608 Apr 2015 8th printing No LEC OM05609 Sep 2015 9th printing No LEC OM05610 No JXC OMT0051 Sep 2016 10th printing No LEC OM05611 No JXC OMT0051 A Jun 2017 11th printing 4 1...