- 25 -
4.3 PLC Setting
Set PLC that become the master station.
Use a PLC that supports CC-Link Ver. 1.10 or Ver. 2.00.
Show a case with CC-Link system master local unit (Q Series) of Mitsubishi for the example about setting.
PC series: QCPU (Q mode), PC type
:
Q00UJ
● Initial addresses of Remote I/O (Rx, Ry) and Remote register (RWr, RWw), etc.
The PLC memory address shown in
“10. Memory assignment”
becomes the address when doing the
setting as the following list. Please set it according to the operating environment.
Example of setting the initial address
Initial addresses
Remote input (Rx)
X1000
Remote output (Ry)
Y1000
Remote register (RWr)
W0
Remote register (RWw)
W1000
Special relay (SB)
SB0
Special register (SW)
SW0
● Station information setting
Set Occupied number of stations of LECPMJ which connected to the PLC.
Please set the value same as Occupied number of stations
of “Optional setting 1” of Basic parameter.
Occupied number of stations
of LECPMJ is set in “2” for shipment.
Example of setting the station information
Station classification
Occupied number of stations
Remote device station
2 stations occupation
●Mode setting
Set the Ver.1 mode.
●Communication speed
Set the same value of communication speed as the value of
“4.1 Switch (STATION NO., B RATE)”
Please refer to the manual of PLC which is using for details of the setting.