- 60 -
(9) The speed / pushing force may vary, depending on the cable length, load and mounting
conditions etc.
If the cable length exceeds 1 m, the speed / pushing force will decrease by a maximum of 10% per
2m. (If the cable length is 5 m: Maximum 20% reduction.)
【
Transportation
】
Caution
(1) Do not pull the cable or drag the product when transporting.
8. Alarm detection
The cause of the alarms is indicated by a combination of lit and flashing ALM and PWR LEDs. When an
alarm has been generated, deactivate the alarm after troubleshooting and after the error has been
corrected by referring to section “8.2 Alarms and countermeasures” (P.61).
Alarms are divided into two types.
-
One can be cleared by resetting (ON-OFF-ON) the SVON input signal.
-
The other can only be cleared by switching off the power supply to the controller.
8. 1 Alarm LED display
The controller uses LED’s to indicate the cause of the alarm when an alarm has been generated.
.
LED
Name of alarm
PWR
ALM
Flashing pattern
Memory error
Flashing
Flashing
Both LED’s flashing alternately by 0.5 seconds
Temperature error
Flashing
Flashing
Both LED’s flashing simultaneously by 0.5 seconds
Over current error
Flashing
ON
PWR LED flashing by 0.5 seconds
Parameter error
ON
Flashing
ALM LED flashing by 0.5 seconds
Return to Origin Position
non-execution error
ON ON
-
LED[PWR]
:
Green
L E D [ A L M ]
:
R e d