-26-
No.PS
※※
-OMV0006-D
Simple Setting Mode
<Operation>
[Simple setting mode (hysteresis mode)]
In the simple setting mode, the set value, hysteresis and delay time can be changed while checking the
current pressure value (main display).
(1) Press and hold the
button between 1 and 3 seconds in measurement mode. [SEt] is displayed on
the main display. When the button is released while in the [SEt] display, the current pressure value is
displayed on the main display, [P_1] or [n_1] is displayed on the sub display (left), and the set value is
displayed on the sub display (right) (Flashing).
(2) Change the set value with
or
button, and press the
button to set the value. Then, the
setting moves to hysteresis setting. (The snap shot function can be used. (Refer to page
.))
(3) Change the set value with
or
button, and press the
button to set the value. Then, the
setting moves to the delay time of the switch output.
(The snap shot function can be used. (Refer to page
.))
(4) The delay time of the switch output can be selected by pressing the
or
button at the ON and
OFF point of the switch output.
Delay time setting can prevent the output from chattering.
The delay time can be set in the range 0.00 to 60.00 sec. in 0.01 sec. increments.
(5) Press the
button for 2 seconds or longer to complete the setting.
(If the button is pressed for less than 2 seconds, the setting will moves to the OUT2 setting.)
∗
1: Selected items (1) to (4) become valid after pressing the
button.
∗
2: After enabling the setting by pressing the
button, it is possible to return to measurement mode by pressing the
button for 2 seconds or longer.
∗
3: When the output mode (refer to page
) is set to error output or output OFF, the simple setting mode cannot be used.
(The setting changes to measurement mode by releasing the button when [SEt] is displayed.)
∗
4: When OUT2 set items are displayed on the sub screen of the measurement mode, step (1) will begin with the OUT2 setting
[P_2] or [n_2].