Chapter 6 Error Message and Troubleshooting
6.2 Troubleshooting
HRZ Series
6-2
6.2 Troubleshooting
The procedure for error recovery varies with alarm types.
Alarm Code.01 to 20, 22, 24, 25:
Eliminate the error cause. Press the [RESET] key on the operation display panel
or power cycle the main breaker to enable error recovery to take effect.
Alarm Code.21, 28:
Eliminate the error cause, and power cycle the main breaker to enable error
recovery to take effect.
Alarm Code.23, 26, 27:
Automatic error recovery is implemented upon elimination of the error.
Alarm Code.24, 26, 27:
This is an alarm for accessories (optional).
No alarm of this type is issued if the system is outfitted with no accessories.
Alarm Code.25, 28:
This alarm is only for HRZ010-W*S.
Table 6-1 Troubleshooting (1/2)
Code
Error message
System
condition
Cause
Remedies
01
Water Leak
Detect FLT
Stop
The fluid is pooled at the base
of this system.
Check for fluid leak.
02
Incorrect Phase
Error FLT
Stop
The power phase rotation is
wrong.
Check that a proper connection
is established between the
power cable and main breaker
of this system.
03
RFGT High
Press FLT
Stop
The pressure of the
refrigerant circuit exceeded
the specified value.
Check that facility water is
being supplied to this system.
04
CPRSR
Overheat FLT
Stop
The temperature in the
compressor was excessive.
Check that facility water is
being supplied to this system.
05
Reservoir Low
Level FLT
Stop
An insufficient amount of the
circulating fluid is observed in
the tank.
Replenish the circulating fluid.
06
Reservoir Low
Level WRN
Continued
An insufficient amount of the
circulating fluid is observed in
the tank.
Replenish the circulating fluid.
07
Reservoir High
Level WRN
Continued
An excessive amount of the
circulating fluid is observed in
the tank.
Drain the circulating fluid.
08
Temp. Fuse
Cutout FLT
Stop
The circulating fluid tank was
raised in temperature.
Check the load specification.
Replacement of the thermal
fuse is required.
Call the supplier for service.
09
Reservoir High
Temp. FLT
Stop
The temperature of the
circulating fluid exceeded the
specified value.
Check the load specification.
11
Reservoir High
Temp. WRN
Continued
The temperature of the
circulating fluid exceeded
your specified value.
Reset the setting temperature.
Содержание HRZ001-H
Страница 6: ...HRX OM I051 Table of Contents HRZ Series TOC 4...
Страница 40: ...HRX OM I051 Chapter 3 Transporting and Installation 3 3 Procedure for Installation HRZ Series 3 16...
Страница 46: ...HRX OM I051 Chapter 4 System Startup and Shutdown 4 5 System Startup and Shutdown HRZ Series 4 6...
Страница 62: ...HRX OM I051 Chapter 5 System Operation 5 4 Examples of System Operation HRZ Series 5 16...
Страница 66: ...HRX OM I051 Chapter 6 Error Message and Troubleshooting 6 2 Troubleshooting HRZ Series 6 4...