HRX-OM-R026
Chapter 5 Display and setting of various functions
HRSH Series
5.5
Inspection monitor menu
5-11
Check of the pressure of the lower pressure side of the refrigerant circuit
6.
Press the [SEL] key once.
The pressure of lower pressure refrigerant circuit is displayed on the digital display.
Displays the pressure of the lower pressure side of the refrigerant circuit.
7.
Press the [SEL] key once.
"- - - - " is displayed on the digital display.
Not used in this product.
Check of the accumulated operation time of the pump
8.
Press the [SEL] key once.
The accumulated operation time of the pump is displayed on the digital display.
Displays the accumulated operation time of the pump. Refer to the table below for the
display.
Table 5.5-2 List of time display
Cumulative time
Indicated value
0h to
999h
to
1,000h to 99,999h
to
100,000h
Return to
AL28 Pump maintenance alarm is generated when the accumulated operation time of the
pump reaches 8,000 hours (
) or more. For details, refer to Chapter 7 Alarm
indication and trouble shooting
PV
SV
PV
SV
PV
SV
Содержание HRSH090 Series
Страница 8: ...HRX OM R026 Contents HRSH Series...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6...
Страница 52: ......
Страница 62: ......
Страница 126: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 20 Alarm customizing function HRSH Series 5 64...
Страница 148: ......
Страница 172: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10...
Страница 177: ...HRX OM R026 Chapter 9 Documents HRSH Series 9 1 Specifications 9 5...
Страница 193: ......