Chapter 4 Starting the Product
4.3
Preparation of circulating fluid
HRSH Series
4-4
4.3 Preparation of circulating fluid
When the circulating fluid tank is filled the user’s machine and piping remains
empty. In that
condition, the circulating fluid flows out to the user’s machine
and piping and the tank level decreases and may require a refill. In that case,
refill the circulating fluid in the following procedure.
1.
Press the [PUMP] key on the operation display panel (press the [RUN/STOP] key and
[MENU] key simultaneously).
The pump operates independently while the [PUMP] key is pressed. The [RUN] lamp
(green) flashes while the pump is operating independently, and the circulating fluid in
the tank is supplied to the cu
stomer’s device and piping. This can be done to check for
leakage, and to discharge air from the piping. If the fluid level in the tank reaches the
lower limit, a buzzer will sound, and alarm no. “AL01 (tank fluid level is low)” is
displayed on the digital display PV. The [ALARM] lamp (red) flashes, the [
] lamp
turns on. In this case, release the alarm referring clause 2.
Fig. 4-3 Manual operation of the pump
Fig. 4-4 Low tank level alarm
If leakage occurs, stop manual operation of the pump and fix the leak.
Flash
Press together
Flash
ON
Содержание HRSH090 Series
Страница 8: ...HRX OM R026 Contents HRSH Series...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6...
Страница 52: ......
Страница 62: ......
Страница 126: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 20 Alarm customizing function HRSH Series 5 64...
Страница 148: ......
Страница 172: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10...
Страница 177: ...HRX OM R026 Chapter 9 Documents HRSH Series 9 1 Specifications 9 5...
Страница 193: ......