HRX-OM-R039
Chapter 4 Starting the Product
HRSE Series
4.3
Preparation of circulating fluid
4-3
4.3 Preparation of circulating fluid
When the circulating fluid tank is filled the user’s machine and piping remains
empty. In that condition, the circulating fluid flows out to the user’s machine
and piping and the tank level decreases and may require a refill. In that case,
refill the circulating fluid in the following procedure.
1.
Press the [PUMP] key on the operation display panel (press the [RUN/STOP] key and
[MENU] key simultaneously).
The pump operates independently while the [PUMP] key is pressed. The [RUN] lamp
(green) flashes while the pump is operating independently, and the circulating fluid in
the tank is supplied to the customer’s device and piping. This can be done to check for
leakage, and to discharge air from the piping.
When the fluid level in the tank drops below the "L" level, stop the operation of the
pump itself, and add some circulating fluid into the tank. Repeat the same sequence
after adding the fluid until the fluid level in the tank stops decreasing. When the liquid
level in the tank stops decreasing, it means that the circulating fluid is filled completely
in the piping of the user's facility.
Fig. 4.3-1 Manual operation of the pump
If leakage occurs due to faulty piping including an opened fitting of eternal piping,
stop manual operation of the pump and fix the leak.
Flash
Press together