HRX-OM-R039
Chapter 3 Transport and Setting Up
3.2
Installation
HRSE Series
3-4
Location that is subjected to strong high frequencies raditation
(microwaves).
Location that is subjected to potential lightning srtike.
Location at altitude of 1000m or higher (except during product storage and
transport).
Location where the product is affected by strong vibrations or impacts.
Condition that applies external force or weight causing the product to be
damaged.
Location without adequate space for maintenance as required.
3.2.2
Location (Required ventilation rate and facility water source)
Installation of multiple products
Keep sufficient space between products so that the air vented from one product will not be taken
in by other products.
Installation Area Ventilation
①
Facility having a large installation area (that can vent the air naturally)
Make an air vent on a wall at a high level and another air vent on a wall at a low level, to
allow for adequate airflow.
②
Facility having a small installation area (that can not vent the air naturally)
Make a forced air exhaust vent on a wall at a high level and an air vent on a wall at a low
level.
Table 3-1 Amount of radiation and required ventilation
Model
Heat
Radiated
kW
Required ventilation amount m
3
/min
Differential temp. of 3
o
C
between inside and
outside of installation area
Differential temp. of 6
o
C
between inside and
outside of installation area
HRSE012-A
-
Approx.
2
40
20
HRSE018-A
-
Approx.
4
70
40
HRSE024-A
-20/23
Approx.
5
90
50
Do not install in a location which can be subjected to any of the
conditions in 3.2.1 Environment.
The product radiates heat from the air vent of the cooling fan.
If the product is operated with insufficient air ventilation the internal
temperature can exceed 35
o
C
, which can cause an overload or affect
the performance and life of the product. To prevent this ensure that
suitable ventilation is available (see below).
Power supply 200/230V : 40°C